STS 4000 Multifunction Test System for Current, Voltage and Power Transformers
The STS 4000 carries out primary tests on current transformers, voltage transformers, power transformers and earthing devices during substation commissioning and maintenance. Primary injection reaches 800 A, and with the BUX 5000 booster the rated figures are up to 5000 A and 7000 A.
- Test objects
- current transformers, voltage transformers, power transformers, earthing devices
- Primary injection current
- 800 A; 5000 A / 7000 A with BUX 5000
- High-voltage AC output
- 2000 V AC
- Low-voltage AC output
- 140 V or 70 V AC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The STS 4000 is a multifunction test system for substation commissioning and maintenance. It tests current transformers, voltage transformers, power transformers and earthing devices, and it runs each test from stored test plans. Results are processed by the PADS software, which produces a condition assessment and a test report.
For current transformers the system measures the turns ratio in voltage mode, polarity, secondary burden, ALF and ISF, the magnetising curve and the knee-point voltage, as well as winding resistance and burden, and it carries out dielectric tests. It also checks Rogowski coils, low-power transformers and transformers with IEC 61850-9 output. Voltage transformers are measured for turns ratio, polarity and secondary burden. For power transformers the system covers turns ratio, vector group, winding resistance, dynamic resistance of the OLTC, magnetising and no-load current, short-circuit voltage and leakage reactance.
The main generator provides an AC high-voltage output up to 2000 V AC for dielectric tests, low-voltage outputs of 140 V or 70 V AC and 65 V DC at 6 A DC, and an output frequency adjustable from 15 to 500 Hz with a resolution of 10 mHz. The measuring inputs accept current up to 10 A AC or DC, and voltages of 300 V AC, 3 V AC and 10 V DC. The timer resolves 1 ms, and the phase angle error is below 0.1°.
The functions are extended by optional modules. The BUX 2000, BUX 3000 and BUX 5000 boosters supply primary injection current, the TD 5000 measures tan delta and capacitance at voltages up to 12 kV, including on generators and motors, and the STCS and STCS PLUS switch the transformer circuits automatically. The STDE demagnetises transformer cores.
Control is local from a 640 by 480 colour TFT display or remotely from a computer over USB or Ethernet. Memory holds up to 64 test plans and more than 1,000 test results. The unit runs from 100 to 230 V with a tolerance of ±15%, draws up to 16 A, and measures 450 × 400 × 230 mm. It works at -10 to 55 °C, with humidity of 5 to 95% without condensation, up to 2000 m altitude, and carries IP 2X protection to IEC 60529, with IP 4X for the high-voltage output.
Technical specifications
| Test objects | current transformers, voltage transformers, power transformers, earthing devices |
|---|---|
| Primary injection current | 800 A; 5000 A / 7000 A with BUX 5000 |
| High-voltage AC output | 2000 V AC |
| Low-voltage AC output | 140 V or 70 V AC |
| Low-voltage DC output | 6 A, 65 V, 360 W |
| Output frequency | 15 to 500 Hz, 10 mHz resolution |
| Tan delta with TD 5000 | maximum 12 kV |
| Measuring inputs | 10 A AC or DC; 300 V AC; 3 V AC; 10 V DC |
| Internal measurement accuracy | below 0.05% of reading, below 0.05% of range |
| Phase angle error | below 0.1° |
| Timer | 1 ms resolution |
| Display | TFT, 640 x 480, 132 x 99 mm |
| Interfaces | USB, Ethernet, IEC 61850-9-2 |
| Memory | up to 64 test plans, more than 1,000 results |
| Mains supply | 100 to 230 V ±15%, up to 16 A |
| Dimensions | 450 x 400 x 230 mm |
| Operating temperature | -10 to 55 °C |
| Humidity | 5 to 95%, non-condensing |
| Protection class | IP 2X, IP 4X for the high-voltage output |
Request a price and lead time
STS 4000 Multifunction Test System for Current, Voltage and Power Transformers. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the maximum primary injection current?
The built-in output reaches 800 A, and with the optional BUX 5000 booster the rated figures are up to 5000 A and 7000 A.
Can tan delta and capacitance be measured?
Yes, with the optional TD 5000 module at voltages up to 12 kV, including on generators and motors.
Does the system support transformers with digital output?
Yes. The system works with the IEC 61850-9-2 protocol and tests current and voltage transformers that have IEC 61850-9 output.