STDE Core Demagnetiser for Power Transformers, 7 A DC and 70 V DC
The STDE removes residual magnetisation from the core of a power transformer once winding resistance has been measured. It feeds direct current of alternating polarity into the winding in line with IEEE 0062 1995 and reverses the current automatically.
- Purpose
- removing residual magnetisation from a power transformer core
- Source type
- DC generator with voltage limit
- Maximum current
- 7 A DC
- Maximum voltage
- 70 V DC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
After the winding resistance has been measured with direct current, the core of a power transformer keeps some residual magnetisation. That magnetisation has to be removed before testing is finished and the transformer returns to service. The STDE is used for exactly this step, bringing the core back to a demagnetised state once the winding resistance measurement is complete.
The principle is to feed direct current of alternating polarity into the transformer winding, as set out in IEEE 0062 1995. The module is built as a DC generator with a voltage limit. Its maximum test current is 7 A DC and its maximum voltage is 70 V DC, and the output stays within 0.5 percent of nominal. The polarity reversal is carried out automatically, so the operator does not swap leads between cycles.
The STDE is an option for the STS 5000 and STS 4000 multifunction test systems and extends their power transformer functions. It works alongside the winding resistance, turns ratio and dynamic tap changer tests that the base system performs. Combined with the STCS PLUS switching module, demagnetisation becomes part of one test sequence run from a single connection. For winding resistance tests on large transformers, the system can be fitted with a separate 20 A DC booster.
The module is housed in a plastic case with a carrying handle. It is connected to the winding of the transformer under test and to the base STS system, and it is intended for commissioning and scheduled testing of power transformers at substations.
Technical specifications
| Purpose | removing residual magnetisation from a power transformer core |
|---|---|
| Source type | DC generator with voltage limit |
| Maximum current | 7 A DC |
| Maximum voltage | 70 V DC |
| Output stability | better than 0.5 percent of nominal value |
| Polarity change | automatic |
| Standard | IEEE 0062 1995 |
| Compatibility | STS 5000, STS 4000 |
| Housing | plastic case with handle |
Part numbers
Show all part numbers (1)
27175
Request a price and lead time
STDE Core Demagnetiser for Power Transformers, 7 A DC and 70 V DC. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
When is demagnetisation of a transformer needed?
After the winding resistance has been measured with direct current, when residual magnetisation remains in the core.
What current does the STDE supply?
Direct current up to 7 A DC with alternating polarity, and the voltage is limited to 70 V DC.
Can the STDE work on its own?
No. The STDE is an option for the STS 5000 and STS 4000 systems and is used together with them.
Similar equipment from other manufacturers