Spark P2 Hand-Held Partial Discharge Surveyor with UHF, HF, UWB and Acoustic Detectors
Spark P2 measures partial discharges and radio interference at substations, transformers, switchgear and cable accessories. It needs no computer for measurement, and its built-in signal processing covers UHF, HF, UWB and acoustic emission detectors.
- Type
- hand-held partial discharge and radio interference surveyor
- Detectors
- narrow-band UHF, HF, UWB, acoustic emission
- UWB bandwidth
- up to 60MHz
- HF bandwidth
- 1MHz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The instrument is used for surveys of substations and for diagnosis of individual equipment, including power transformers, air and gas insulated switchgear, rotating machines and cable accessories. Measurements can be taken when equipment is commissioned or while it is in service. At 5.6 lbs it is lighter than a laptop, and its 7h battery means no computer is needed in the field.
A narrow-band UHF detector sits alongside HF, UWB and acoustic detectors. Amplifiers, attenuators, filters and frequency converters are built in and controlled in software, so no external signal conditioning accessories are required. External amplifiers and sensors with built-in amplifiers draw their power directly from the instrument.
For a substation survey the UHF mode uses a monopole or directional antenna to locate partial discharge sources from a safe distance, without contact with the equipment. The narrow-band UHF tuner is more sensitive than frequency-conversion methods and suits transformers and gas insulated switchgear fitted with UHF sensors. Switchgear is checked with TEV sensors on individual cubicle enclosures and with acoustic sensors. High-frequency current transformers, HFCT, are fitted on the earth connections of cable accessories, transformers and circuit breakers, and ultrasonic microphones detect discharges in liquid and gas insulation. The instrument connects directly to capacitive couplers to obtain the discharge signal and a timing reference, and the optional UWB detector measures the integrated charge of pulses.
On a transformer several methods are combined on site: HFCT clamps on the earthing of the tank and neutral for analysis in the HF and UWB ranges, internal UHF sensors for the radio emission of discharges inside the tank, and acoustic sensors on the tank walls. Suspect equipment found during a substation survey is then examined with the UWB and acoustic emission detectors. Wizard Mode guides users with no special training through set templates with automatic HF and UHF data collection, while Expert Mode opens every detector setting and analysis tool, including spectral analysis, time analysis, phase-resolved analysis and analysis of signal components. Data are transferred to the manufacturer's software for analysis, visualisation and reporting.
Technical specifications
| Type | hand-held partial discharge and radio interference surveyor |
|---|---|
| Detectors | narrow-band UHF, HF, UWB, acoustic emission |
| UWB bandwidth | up to 60MHz |
| HF bandwidth | 1MHz |
| UHF bandwidth | 6MHz |
| Sweep time | less than 5 seconds |
| Sensors | UHF antennas, TEV, HFCT, ultrasonic microphones, capacitive couplers |
| Modes | Wizard Mode, Expert Mode |
| Battery life | 7h |
| Weight | 5.6 lbs |
| Applications | transformers, switchgear, rotating machines, cable accessories, substations |
Request a price and lead time
Spark P2 Hand-Held Partial Discharge Surveyor with UHF, HF, UWB and Acoustic Detectors. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Is a laptop needed to operate the Spark P2?
No. The instrument runs on its 7h battery, and a computer is only needed for later analysis and reporting.
Which sensors are used to survey switchgear?
TEV sensors on individual cubicle enclosures and acoustic sensors, plus internal UHF sensors and HFCT for gas insulated switchgear.
Can staff without partial discharge measurement experience use the instrument?
Yes. Wizard Mode guides measurements through templates with automatic HF and UHF data collection.