SCAR 10 Tester for Live Metal-Oxide Arrester Diagnostics with Third Harmonic Analysis

The SCAR 10 measures leakage current in metal-oxide arresters without disconnecting them from the network and analyses the third harmonic with compensation. The kit includes a measuring instrument and a C 47-IS clamp-on transformer.

Measurement method
IEC 60099-5 A1, clause 6, methods B1 and B2
Measured quantities
RMS and peak total current, RMS third harmonic, temperature
Total current ranges
1.999 mA (lower band, up to 1 mA), 19.99 mA (upper band)
Third harmonic ranges
199.9 µA below 0.1 mA and 1999 µA above that

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The SCAR 10 is used for routine checks on metal-oxide arresters fitted to high-voltage transmission lines and distribution equipment. Measurements follow IEC 60099-5 A1, clause 6, methods B1 and B2, and the arrester stays in service, so the line does not have to be switched off.

A clamp-on transformer, the C 47-IS, encircles the earth conductor of the arrester and measures the leakage current. That current is normally from a fraction of a milliampere up to a few milliamps and contains a third harmonic whose level indicates deterioration of the arrester. The resistive part of the current grows with ageing under various loads and can eventually lead to failure. The C 47-IS is built for measurements in strong electric and magnetic fields.

If the third harmonic may originate from distortion of the network voltage rather than from the arrester itself, an auxiliary probe in the kit records the harmonic content of the voltage so that it can be compensated. On high-voltage lines the voltage distortion is usually small compared with the arrester limit, so compensation is rarely needed there. On medium-voltage arresters the instrument is connected to the secondary winding of the line voltage transformer under test.

The instrument reports the RMS and peak values of the total current, the RMS value of the third harmonic and the temperature. The total current span covers 1.999 mA at the lower end, up to 1 mA, and 19.99 mA above that, and the switch between them is automatic. The third harmonic ranges are 199.9 µA and 1999 µA. The 3.5-digit backlit LCD shows the unit in µA or mA with an LED, and a battery-discharge indicator is included.

The instrument runs on four AA alkaline batteries and lasts over 50 hours at 10% backlight, or 25 hours with continuous backlight. The measuring instrument weighs 0.75 kg, the clamp-on transformer 0.9 kg, and the whole set travels in a case weighing 3 kg. It complies with Directives 2004/108/EC and 2006/95/EC, EN 61326:2006 and CEI EN 61010-1.

Technical specifications

Measurement methodIEC 60099-5 A1, clause 6, methods B1 and B2
Measured quantitiesRMS and peak total current, RMS third harmonic, temperature
Total current ranges1.999 mA (lower band, up to 1 mA), 19.99 mA (upper band)
Third harmonic ranges199.9 µA below 0.1 mA and 1999 µA above that
Accuracy at 50/60 Hz, 0.1 to 10 mA±5%
Accuracy at 150/180 Hz, 10 to 1000 µA±10%
Calibration output1 mA peak at 50 (60) Hz
Nominal frequency50 Hz (60 Hz on request)
Display3.5-digit LCD with backlight
Power supplyfour AA alkaline batteries
Battery lifeover 50 hours at 10% backlight, 25 hours with continuous backlight
Operating temperature0 to 50 °C
Storage temperature-25 °C to 70 °C
Measuring instrument200 × 112 × 65 mm, 0.75 kg
Clamp-on transformer C 47-ISratio 1000:1, load 47 ohm, tightening diameter 54 mm, jaw opening over 55 mm, 0.9 kg
Carry case450 × 320 × 110 mm, 3 kg

Part numbers

Show all part numbers (1)

11142

Request a price and lead time

SCAR 10 Tester for Live Metal-Oxide Arrester Diagnostics with Third Harmonic Analysis. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does the arrester have to be taken out of service for the measurement?

No. The SCAR 10 measures the leakage current through the C 47-IS clamp-on transformer on the earth conductor while the arrester remains under working voltage.

How are network voltage harmonics taken into account at medium voltage?

An auxiliary probe is connected to the secondary winding of the line voltage transformer, and the instrument compensates the third harmonic of the voltage.

What accuracy does the current measurement have?

The accuracy is ±5% at 50/60 Hz in the 0.1 to 10 mA range and ±10% for the third harmonic at 150/180 Hz in the 10 to 1000 µA range.