RELTEST 1000 Protection Relay Tester with Four Voltage and Two Current Outputs
RELTEST 1000 tests protection relays in distribution networks, smart grids and renewable energy plants. It provides three independent voltage outputs from 0 to 400 V AC, a fourth voltage output up to 130 V AC, a current output up to 15 A and a 40 to 400 Hz frequency generator.
- Three independent voltage outputs
- 0 to 400 V AC
- Fourth voltage output
- 0 to 13 V or 0 to 130 V AC
- Fourth output accuracy
- ±0.5% of reading, ±0.2% of full scale
- Voltage output rating
- 20 VA (three outputs), 6 VA (fourth output)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The set is used to check protection relays in distribution networks, smart grids and renewable energy plants. It covers distribution relays, single-phase and three-phase devices, low-power units and protective equipment, including functions coded ANSI 21, 25, 27/59, 32, 50, 51, 67, 79 and 81. These cover distance protection, synchronising checks, under and over voltage, directional power, overcurrent cut-offs, directional overcurrent, auto-reclosing and frequency protection.
The three independent voltage outputs are adjustable from 0 to 400 V AC and share a neutral that is isolated from both the supply and earth, each rated 20 VA continuously at maximum voltage. The fourth independent output has two ranges, 0 to 13 V and 0 to 130 V AC, with separately set amplitude and phase. Its accuracy is ±0.5% of reading plus ±0.2% of full scale, with resolution of 6 mV and 60 mV, distortion of 0.1%, and a phase angle that runs from 0° to 360° in 0.5° steps with an accuracy of 1°. This output is rated 6 VA.
The main current output provides 0 to 15 A AC and switches between three sockets. A second independent current output is adjustable from 0 to 1.5 A AC. The frequency generator operates across 40 to 400 Hz, and an auxiliary generator supplies up to 110 V DC. Two digital inputs measure tripping time, four auxiliary digital outputs are fitted, and an optional generator with six low-level outputs is available.
Control is local from the keyboard and colour display, or remote from a PC through the Advanced Test & Data Management Software. The operator selects the required test from a menu, results are kept in internal memory and passed to a PC over USB, and the test record is generated automatically.
The unit weighs 13 kg and measures 46 (W) x 35 (H) x 17 (D) cm, running from a 195 to 264 V AC 50/60 Hz supply. It operates from 0 to 50 °C, stores from -20 °C to 70 °C, and tolerates 5 to 95% relative humidity without condensation. It complies with EN 61326-1 with A1 and A2 amendments, CEI EN 61010-1, and Directives 2004/108/EC and 2006/95/EC.
Technical specifications
| Three independent voltage outputs | 0 to 400 V AC |
|---|---|
| Fourth voltage output | 0 to 13 V or 0 to 130 V AC |
| Fourth output accuracy | ±0.5% of reading, ±0.2% of full scale |
| Voltage output rating | 20 VA (three outputs), 6 VA (fourth output) |
| Main current output | 0 to 15 A AC, switched between three sockets |
| Second current output | 0 to 1.5 A AC |
| Frequency generator | 40 to 400 Hz |
| Auxiliary voltage | up to 110 V DC |
| Digital inputs and outputs | 2 timing inputs, 4 auxiliary outputs |
| Interface | USB |
| Weight | 13 kg |
| Dimensions | 46 (W) x 35 (H) x 17 (D) cm |
| Mains supply | 195 to 264 V AC 50/60 Hz |
| Operating temperature | 0 to 50 °C |
| Storage temperature | -20 °C to 70 °C |
| Relative humidity | 5 to 95%, non-condensing |
| Standards | EN 61326-1 with A1 and A2 amendments, CEI EN 61010-1, Directives 2004/108/EC and 2006/95/EC |
Part numbers
Show all part numbers (1)
RELTEST 1000
Request a price and lead time
RELTEST 1000 Protection Relay Tester with Four Voltage and Two Current Outputs. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which protection functions can the RELTEST 1000 test?
It covers ANSI 21, 25, 27/59, 32, 50, 51, 67, 79 and 81, including distance, synchronising, voltage, directional power, overcurrent, directional overcurrent, auto-reclosing and frequency protection.
What current can the set deliver?
The main output supplies 0 to 15 A AC through three switched sockets, and a second independent output is adjustable up to 1.5 A AC.
How is the set operated?
Locally from the keyboard and colour display, or remotely from a PC over USB using the Advanced Test & Data Management Software.