RCTD Compensating Reactor for TD 5000 Tan Delta Testing of Rotating Machines
The RCTD complements the TD 5000 when tan delta is measured on the insulation of rotating machines. It compensates the capacitive load, raises the test current and allows the maximum test voltage to be reached on high-capacitance objects.
- Type
- compensating reactor
- Application
- tan delta measurement on rotating machines with TD 5000
- Contents
- two inductor coils
- Nominal inductance per coil
- 40 H
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The RCTD is a compensating reactor that works alongside the TD 5000 when the dissipation factor (tan delta) of insulation in rotating machines is measured. Generator and motor windings present a large capacitance, and without compensation the test source cannot raise the voltage to the required level. The reactor offsets this capacitive part of the load, so a higher test current can be drawn and the full test voltage becomes reachable on high-capacitance objects.
Each unit contains two inductor coils rated at 40 H. The unit carries a steady current of 0.4 A, and each inductor can take up to 1 A for more than 10 s, which covers the duration of a typical measurement. The coils are connected in parallel with the load under test.
Two units can be joined in parallel for larger objects, which gives three or four coils with a combined rating of 2 x 80 H. The number of coils in circuit is chosen to suit the capacitance of the winding being tested. The TD 5000 is an optional module for capacitance and tan delta measurement within the STS 5000 multifunction test system, which supplies up to 12 kV.
The reactor is supplied in a transport case, while the connection kit is a separate item with its own order code. Both codes, 47175 and 48175, are listed in the specification table.
Technical specifications
| Type | compensating reactor |
|---|---|
| Application | tan delta measurement on rotating machines with TD 5000 |
| Contents | two inductor coils |
| Nominal inductance per coil | 40 H |
| Steady current | 0.4 A |
| Maximum current per coil | 1 A |
| Duration at maximum current | more than 10 s |
| Two RCTD units in parallel | three or four coils, 2 x 80 H |
| Compatibility | TD 5000 (STS 5000 module, up to 12 kV) |
| 47175 | RCTD in a transport case |
| 48175 | connection kit for the RCTD |
Part numbers
Show all part numbers (3)
RCTD, 47175, 48175
Request a price and lead time
RCTD Compensating Reactor for TD 5000 Tan Delta Testing of Rotating Machines. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Why is an RCTD needed when measuring tan delta on generators?
It offsets the large winding capacitance, raises the test current and lets the TD 5000 reach its maximum test voltage.
What are the coil ratings?
Two 40 H inductors, a steady current of 0.4 A, and up to 1 A per inductor for more than 10 s.
Can several reactors be combined?
Yes. Two RCTD units can be connected in parallel to give three or four coils with a combined rating of 2 x 80 H.