RCL-19 and RCL-47 Recloser and Sectionaliser Test Systems, 19 and 47 kVA

Systems for verifying automatic reclosers in simulated short-circuit conditions. They have an adjustable high current output, a computer-controlled impedance compensation circuit and a measuring section for reclosers of the direct acting type, single or three phase, and for sectionalisers.

Purpose
testing of reclosers and sectionalisers
RCL-19 output
19 kVA
RCL-47 output
47 kVA
Equipment tested
direct acting reclosers, single and three phase types, sectionalisers, reclosers with electronic control

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

RCL-19 and RCL-47 are used to check that automatic circuit reclosers operate correctly under simulated short-circuit conditions. The sets can test nearly every direct acting recloser and sectionaliser, single or three phase, and they also perform primary injection on reclosers with electronic control. The two models differ in output power: 19 kVA in the RCL-19 and 47 kVA in the RCL-47.

Each set combines an adjustable high current source, a computer-controlled impedance compensation circuit and measuring equipment. Measurements are made with high accuracy, showing the full waveform and the true RMS value of the current pulse. A desktop computer and the WIN RCL software are included in the supply.

The minimum trip current is determined automatically: the current through the recloser coil rises until tripping begins, the computer records that value, which is usually about twice the coil rating, and the current then rises to lock-out. Time-current characteristic tests apply the recommended current levels and measure trip current, trip time, reclose time and total interruption time. A sequence of operations test counts the cycles to lock-out and warns if there are too many or too few. Sectionalisers are checked with current pulses that imitate the operation of a recloser.

Test profiles store current levels, tap and vernier positions for each recloser type in a template library. On a repeat test the vernier is set automatically, so manual trimming of the current is not needed. All records are kept in a history, which can be sorted, searched by value and printed after preview. Protection includes a circuit breaker, overload, overheating and short-circuit protection, an emergency stop button and a safety circuit. The output is disconnected if the recloser exceeds the permitted time to lock-out, and a red-green indicator shows the state of the output current. The frame has braked wheels, a towing ring, lifting eyes and a printer port. ISO 17025 calibration is available on request.

Technical specifications

Purposetesting of reclosers and sectionalisers
RCL-19 output19 kVA
RCL-47 output47 kVA
Equipment testeddirect acting reclosers, single and three phase types, sectionalisers, reclosers with electronic control
Outputadjustable high current, impedance compensation
Measurementfull waveform, true RMS value of current pulse
Testsminimum trip current, time-current characteristic, sequence of operations, trip and reclose times, total interruption time, sectionaliser lock-out
Controldesktop computer, WIN RCL software
Protectioncircuit breaker, overload, overheating, short circuit, emergency stop
CalibrationISO 17025 on request

Part numbers

Show all part numbers (2)

RCL-19, RCL-47

Request a price and lead time

RCL-19 and RCL-47 Recloser and Sectionaliser Test Systems, 19 and 47 kVA. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How do RCL-19 and RCL-47 differ?

By output power: 19 kVA in the RCL-19 and 47 kVA in the RCL-47, with the same range of tests in both models.

Can reclosers with electronic control be tested?

Yes, the sets perform primary injection on reclosers with electronic control.

How is a repeat test sped up?

Templates store current levels, tap and vernier positions, and the vernier is set automatically on repeat tests.