PSC82502201 sub-transmission optical sensor for 46 to 69 kV overhead lines
PSC82502201 is an optical sensor for overhead sub-transmission networks rated 46 to 69 kV. Together with a remote terminal unit (RTU), it measures bidirectional power flow and power quality indicators and records fault events, and it can operate within a SCADA system with automatic sectionalising.
- Model
- PSC82502201
- Type
- optical current and voltage sensor
- Voltage class
- 46–69 kV
- BIL
- 350 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The PSC82502201 sensor is fitted on overhead lines in the 46 to 69 kV class. The sensor kit, together with the RTU, measures power flow in both directions, monitors power quality and sends messages about fault events. Monitoring is carried out in real time on three phases, covering voltage, current and short-circuit events, with the direction of current taken into account.
Measurement is performed by an optical method, which gives high accuracy. For field crews, this reduces the hazard when working near the sensor, and for the line it lowers the fire risk from the equipment. The housing is made of HCEP, a hydrophobic cycloaliphatic epoxy resin designed for outdoor installation.
The sensor can be used on its own to monitor faults and power quality on the line. The second option combines it with a motor drive and a disconnector, and in that case it forms part of an automatic sectionalising system under SCADA control. The automatic sectionalising option is intended to reduce the total duration of supply interruptions, measured by SAIDI.
Sensors are placed on network sections between substations, where dispatchers need to see the direction of power flow and the location of a fault. Event messages from several points on the line shorten the time needed to find a damaged section, and power quality data supports analysis of network performance. The unit has a BIL of 350 kV, is 30 in high and weighs 85 lb, and its operating range is -4 to +65 °C.
During design, the installation points on the line, the communication channel between the RTU and the control centre, and the equipment set (measurement only, or measurement with automatic sectionalising) must be decided. Selecting the variant requires only the line voltage class and the functions needed.
Technical specifications
| Model | PSC82502201 |
|---|---|
| Type | optical current and voltage sensor |
| Voltage class | 46–69 kV |
| BIL | 350 kV |
| Measurements | bidirectional voltage and current on three phases; power quality; fault events |
| Housing material | HCEP hydrophobic cycloaliphatic epoxy resin |
| Integration | RTU, SCADA, optional automatic sectionalising |
| Height | 30 in |
| Weight | 85 lb |
| Operating temperature | -4 to +65 °C |
Part numbers
Show all part numbers (1)
PSC82502201
Request a price and lead time
PSC82502201 sub-transmission optical sensor for 46 to 69 kV overhead lines. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the sensor work without switching equipment?
Yes. It can be used on its own to monitor fault events and power quality, while the motor drive and disconnector are needed only for automatic sectionalising.
Which quantities does the sensor measure?
Voltage and current on three phases, taking into account the direction of power flow, together with power quality indicators and fault events.
What voltage class is the PSC82502201 designed for?
Overhead lines of 46 to 69 kV, with a BIL of 350 kV.