PSC82011100 Line Post Current Sensor, 15 kV, 600 A:10 V, Current Only

The PSC82011100 is a line post insulator rated at 15 kV with built-in current measurement. Its body is cycloaliphatic epoxy, and the output is a low energy analogue (LEA) signal with a 600 A to 10 V ratio.

Type
Line post current sensor
Version
Current Only (CMI)
Voltage class
15 kV
Current ratio
600 A to 10 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The line post sensor is mounted on a pole of an overhead distribution line, in place of the standard post insulator. It holds the conductor and converts the current in the conductor into a weak analogue signal for measurement, protection and network automation devices. The product belongs to the measurement systems group for electrical networks and is rated for a 15 kV voltage class.

The body is formed from cycloaliphatic epoxy resin, which gives high insulation properties at a low mass. The conductor is laid in a groove on the upper part, secured with clamps and closed with a swivel latch. A plate for connecting earth is provided on the underside.

The Current Only (CMI) version measures current with a ratio of 600 A to 10 V. The manufacturer's description of this sensor also lists a voltage ratio of 10000:1 and refers to voltage measurement, so when ordering, confirm separately whether a voltage channel is needed or whether the current channel alone is sufficient.

The output is a low energy analogue (LEA) signal, meaning a voltage proportional to the current, rather than a secondary current as in a conventional current transformer. The signal is fed directly to the LEA inputs of control and metering equipment, without intermediate transformers or shunts. The length and type of connecting cable should be agreed with the requirements of the receiving device.

Selection requires the line voltage class, the operating current range, the type of receiving device with LEA inputs and the method of mounting on the pole. Installation consists of fitting the sensor to the crossarm, laying the conductor in the groove, tightening the clamps and connecting the earth.

Technical specifications

TypeLine post current sensor
VersionCurrent Only (CMI)
Voltage class15 kV
Current ratio600 A to 10 V
Voltage ratio (per description)10000:1
OutputLow Energy Analog (LEA)
Body materialCycloaliphatic epoxy
Conductor fixingGroove and clamps, swivel latch
EarthingEarthing plate

Part numbers

Show all part numbers (1)

PSC82011100

Request a price and lead time

PSC82011100 Line Post Current Sensor, 15 kV, 600 A:10 V, Current Only. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What output signal does the sensor give?

A low energy analogue (LEA) signal, with 10 V corresponding to a current of 600 A.

Does the sensor measure voltage?

The Current Only (CMI) version measures current. The manufacturer's description gives a voltage ratio of 10000:1, so confirm whether a voltage channel is needed when ordering.

How is the conductor secured?

The conductor is laid in a groove, secured with clamps and closed with a swivel latch, and the earth is connected to the earthing plate.