PSC82011100 Line Post Current Sensor, 15 kV, 600 A:10 V, Current Only
The PSC82011100 is a line post insulator rated at 15 kV with built-in current measurement. Its body is cycloaliphatic epoxy, and the output is a low energy analogue (LEA) signal with a 600 A to 10 V ratio.
- Type
- Line post current sensor
- Version
- Current Only (CMI)
- Voltage class
- 15 kV
- Current ratio
- 600 A to 10 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The line post sensor is mounted on a pole of an overhead distribution line, in place of the standard post insulator. It holds the conductor and converts the current in the conductor into a weak analogue signal for measurement, protection and network automation devices. The product belongs to the measurement systems group for electrical networks and is rated for a 15 kV voltage class.
The body is formed from cycloaliphatic epoxy resin, which gives high insulation properties at a low mass. The conductor is laid in a groove on the upper part, secured with clamps and closed with a swivel latch. A plate for connecting earth is provided on the underside.
The Current Only (CMI) version measures current with a ratio of 600 A to 10 V. The manufacturer's description of this sensor also lists a voltage ratio of 10000:1 and refers to voltage measurement, so when ordering, confirm separately whether a voltage channel is needed or whether the current channel alone is sufficient.
The output is a low energy analogue (LEA) signal, meaning a voltage proportional to the current, rather than a secondary current as in a conventional current transformer. The signal is fed directly to the LEA inputs of control and metering equipment, without intermediate transformers or shunts. The length and type of connecting cable should be agreed with the requirements of the receiving device.
Selection requires the line voltage class, the operating current range, the type of receiving device with LEA inputs and the method of mounting on the pole. Installation consists of fitting the sensor to the crossarm, laying the conductor in the groove, tightening the clamps and connecting the earth.
Technical specifications
| Type | Line post current sensor |
|---|---|
| Version | Current Only (CMI) |
| Voltage class | 15 kV |
| Current ratio | 600 A to 10 V |
| Voltage ratio (per description) | 10000:1 |
| Output | Low Energy Analog (LEA) |
| Body material | Cycloaliphatic epoxy |
| Conductor fixing | Groove and clamps, swivel latch |
| Earthing | Earthing plate |
Part numbers
Show all part numbers (1)
PSC82011100
Request a price and lead time
PSC82011100 Line Post Current Sensor, 15 kV, 600 A:10 V, Current Only. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What output signal does the sensor give?
A low energy analogue (LEA) signal, with 10 V corresponding to a current of 600 A.
Does the sensor measure voltage?
The Current Only (CMI) version measures current. The manufacturer's description gives a voltage ratio of 10000:1, so confirm whether a voltage channel is needed when ordering.
How is the conductor secured?
The conductor is laid in a groove, secured with clamps and closed with a swivel latch, and the earth is connected to the earthing plate.
Similar equipment from other manufacturers