PM5A3 insulation analyser, insulation resistance up to 5 TΩ, voltmeter to 1000 V

The PM5A3 measures insulation resistance up to 5 TΩ and runs automated tests for absorption index, polarisation index, capacitance, leakage current, step voltage and ramp. Its AC and DC voltmeter reads 1000 V true RMS at most, and the pass/fail mode speeds up routine checks.

Type
insulation analyser
Insulation resistance measurement
up to 5 TΩ
AC and DC voltmeter
true RMS, 1000 V maximum
Automated tests
absorption index, polarisation index, capacitance, leakage current, step voltage, ramp

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The analyser is used to assess the insulation condition of electrical equipment in the laboratory and in the field. One instrument covers several kinds of measurement, from a quick threshold check to extended automated tests, and results from the same equipment are compared over time.

The upper limit for insulation resistance is 5 TΩ. A microprocessor sequences the measurements, the range is picked automatically, and a circuit suppressing external interference reduces induced effects at substations and machine halls where energised equipment stands nearby. A battery supply keeps the analyser self-contained.

Automated tests cover the absorption index and polarisation index, from which moisture and contamination of the insulation are judged, together with capacitance and leakage current measurements. Step voltage changes and linear ramp mode show how the insulation behaves as the applied voltage rises, and can reveal defects that appear only at higher voltage levels.

The pass/fail mode compares the measured value with a set limit. It is applied in repeated checks on large numbers of objects where only a verdict of conformity is needed.

The built-in AC and DC voltmeter works with true RMS values up to 1000 V. Before connection it confirms that there is no voltage on the object, and after a test it checks any residual voltage. The analyser conforms to IEC requirements. The same family includes the PM1A and PM10A3, which differ in their resistance limits and voltmeter ranges.

Technical specifications

Typeinsulation analyser
Insulation resistance measurementup to 5 TΩ
AC and DC voltmetertrue RMS, 1000 V maximum
Automated testsabsorption index, polarisation index, capacitance, leakage current, step voltage, ramp
Test modepass / fail
Controlmicroprocessor
Range selectionautomatic
Interference immunitysuppression of external interference
Power supplybattery
ComplianceIEC

Part numbers

Show all part numbers (1)

PM5A3

Request a price and lead time

PM5A3 insulation analyser, insulation resistance up to 5 TΩ, voltmeter to 1000 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What is the highest insulation resistance the PM5A3 measures?

The upper limit is 5 TΩ, and the measuring range switches automatically.

What does the built-in voltmeter measure?

AC and DC voltage up to 1000 V, with true RMS measurement.

Which automated tests does the analyser run?

Absorption index, polarisation index, capacitance, leakage current, step voltage and ramp tests.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides