International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

PM15-2 DC high voltage test set with megohmmeter, up to 15 kV

The PM15-2 supplies an adjustable DC voltage up to 15 kV to isolated electrical equipment and measures the leakage current through the insulation to earth. Insulation resistance up to 3000000 MΩ is read directly from the scale at 5 kV, 10 kV or 15 kV DC.

Type
high voltage test set with megohmmeter
Output voltage
up to 15 kV DC, adjustable
Test voltages for resistance measurement
5 kV, 10 kV or 15 kV DC
Leakage current measurement
0.01–2000 µA DC

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The set tests the insulation of generators, transformers, motors, cables and switchgear, among other electrical equipment. It works both as a DC test voltage source and as a measuring instrument, so one unit serves for dielectric withstand testing and for judging insulation condition from leakage current.

The PM15-2 generates a regulated voltage up to 15 kV DC and applies it to the test object. The current flowing through the main insulation to earth is shown on a pointer instrument on the front panel, across a range from 0.01 to 2000 µA DC. In the PM15-4 version the top of that scale is 4000 µA. At 5 kV, 10 kV or 15 kV DC, the insulation resistance up to 3000000 MΩ is read straight from the same panel.

The housing is light and strong, designed for many years of field use. The pointer instruments are easy to read and the controls are simple, so preparing a measurement takes little time. The design allows tests with either AC or DC voltage.

Typical tasks include dielectric withstand testing, measurement of leakage current, and checking insulation to earth. The set is also used as an auxiliary device when locating cable faults alongside the main equipment. Repeated measurements on the same equipment show how the leakage current changes over time, which supports planning repairs according to the actual condition.

Next to the PM15-2 in the range of megohmmeter test sets are the PAD56, rated 5 kV AC / 6 kV DC, and the PAD10-25, rated 10 kV AC / 25 kV DC. The choice between them depends on the voltage class of the equipment and on whether the test uses AC or DC voltage.

Technical specifications

Typehigh voltage test set with megohmmeter
Output voltageup to 15 kV DC, adjustable
Test voltages for resistance measurement5 kV, 10 kV or 15 kV DC
Leakage current measurement0.01–2000 µA DC
Leakage current, PM15-4 versionup to 4000 µA DC
Insulation resistance measurementup to 3000000 MΩ
Indicationpointer instruments on front panel
Test typeAC and DC
Test objectsgenerators, transformers, motors, cables and switchgear

Part numbers

Show all part numbers (2)

PM15-2, PM15-4

Request a price and lead time

PM15-2 DC high voltage test set with megohmmeter, up to 15 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What leakage current range does the PM15-2 show?

From 0.01 to 2000 µA DC directly on the front panel instrument; the PM15-4 version has a scale up to 4000 µA.

At which voltages is insulation resistance read?

Resistance up to 3000000 MΩ is read directly at 5 kV, 10 kV or 15 kV DC.

Is the set suitable for locating cable faults?

Yes, it is used as an auxiliary device when searching for cable damage alongside the main equipment.