PD Hub data acquisition unit for continuous PD monitoring, IP65 or IP68

The PD Hub is a distributed acquisition unit for a partial discharge monitoring system. It processes signals from the PD sensors fitted to the equipment and sends the data to a central unit over fibre optic cable.

Type
distributed data acquisition unit for PD monitoring
Sensors per PD Hub
groups of three, six, nine or twelve
Acquisition unit
PDCheck or PDScope
Protection rating
IP65; IP68 version

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Continuous partial discharge monitoring of major electrical plant relies on distributed acquisition units, and the PD Hub is one of them. It serves generators, power transformers, high voltage cables and GIS. A monitoring system normally combines one central unit with several PD Hubs, each handling the signals from the sensors on its own asset.

One PD Hub is fitted for every group of three, six, nine or twelve PD sensors. It houses a PDCheck or PDScope acquisition box inside an IP65 cabinet and is mounted close to the equipment under observation. Keeping the unit near the asset shortens the runs that carry high frequency discharge signals from the sensors.

Every PD Hub links to the central unit in the control room over a fibre optic network. Light carries the data, so the link is immune to electromagnetic interference in the substation and electrically separates the acquisition units from the central equipment. Discharge data are collected, stored and processed in the central unit.

A PD Hub can also run as a standalone monitor for one asset without a wider network. In that mode it keeps the data in internal memory, from which they can be downloaded at any time for detailed evaluation. This suits a single transformer or generator where no monitoring network is in place.

Besides the standard IP65 version, the PD Hub is available with an IP68 rating for installations in flooded or damp conditions. Typical applications include rotating machines, variable speed drives, power transformers, GIS, MV and HV cables, and MV and LV switchgear.

Technical specifications

Typedistributed data acquisition unit for PD monitoring
Sensors per PD Hubgroups of three, six, nine or twelve
Acquisition unitPDCheck or PDScope
Protection ratingIP65; IP68 version
Link to central unitfibre optic network
Standalone modeinternal data storage, downloadable at any time
Applicationsrotating machines, VSD drives, power transformers, GIS, MV and HV cables, MV and LV switchgear

Request a price and lead time

PD Hub data acquisition unit for continuous PD monitoring, IP65 or IP68. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many sensors connect to one PD Hub?

One PD Hub is fitted for each group of three, six, nine or twelve PD sensors.

Can a PD Hub work without a central unit?

Yes, as a standalone monitor whose data are stored internally and downloaded for evaluation at any time.

Which version suits installations exposed to flooding or moisture?

Besides the standard IP65 cabinet, a version with IP68 protection is available.