PCI-600 — programmable 10–600 A primary current source for relay testing
The PCI-600 is a programmable AC current source for substation work. It injects a current from 10 to 600 A, measures it through an isolated current transformer and records the operating time of protective devices.
- Type
- Programmable AC current source for primary injection
- Test current
- 10–600 A
- Built-in ammeter
- 100 mA – 1000 A, 1 % of reading ±20 mA
- Measuring method
- Isolated current transformer
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The PCI-600 is mainly used to check protective relays by primary current injection at power utility substations. The same unit tests thermal, electromagnetic and electronic motor protection relays and moulded-case circuit breakers, measures primary and secondary currents of current transformers, and serves other tasks that need a high-current source.
The unit generates an AC test current from 10 to 600 A. The built-in current meter covers 100 mA to 1000 A with an accuracy of 1 % of reading ±20 mA, measured through an isolated current transformer. A separate external current input covers 10 mA to 10 A with an accuracy of 1 % of reading ±2 mA. Results are shown on a backlit four-line display with twenty characters per line.
The built-in timer measures intervals from 1 ms to 2 hours with an accuracy of 0.1 % of reading ±1 ms. The timer can be stopped by a voltage of 24–300 V DC or peak AC, by a dry contact, or by the loss of primary current, which determines the time delay before a protective relay operates.
The supply is 100–120 V AC or 200–240 V AC, 50/60 Hz, and the voltage is set at the factory. Models are ordered as 9029-UC for 110 V or 9058-UC for 220 V. An RS-232C port at 19200 baud is used for factory calibration and diagnostics. The design is built to IEC 61010 (1995), with UL 61010A-1 and CSA-C22.2 also satisfied.
The dimensions are 42.6 x 32.0 x 27 cm and the weight is 21 kg. Operating temperature runs from -10 to 50 °C and storage from -30 to 70 °C, with specifications stated at nominal voltage and +25 °C. The kit includes 10 ft #1/0 AWG test leads, a mains cord and an earth cable. A transport case is available as an option, and the 8000-0070, 8000-0110, 8000-0107 and 8000-0085 cable sets are available separately.
Technical specifications
| Type | Programmable AC current source for primary injection |
|---|---|
| Test current | 10–600 A |
| Built-in ammeter | 100 mA – 1000 A, 1 % of reading ±20 mA |
| Measuring method | Isolated current transformer |
| External current input | 10 mA – 10 A, 1 % of reading ±2 mA |
| Timer | 1 ms – 2 hours, 0.1 % of reading ±1 ms |
| Timer stop | 24–300 V DC or peak AC, dry contact, or loss of primary current |
| Display | Backlit LCD, 4 lines of 20 characters |
| Supply | 100–120 V AC or 200–240 V AC (factory set), 50/60 Hz |
| Interface | RS-232C (19200 baud) for calibration and diagnostics |
| Dimensions | 42.6 x 32.0 x 27 cm |
| Weight | 21 kg |
| Operating temperature | -10 to 50 °C |
| Storage temperature | -30 to 70 °C |
| Safety | IEC 61010 (1995), with UL 61010A-1 and CSA-C22.2 |
| Supplied with | #1/0 AWG leads 10 ft, mains cord, earth cable |
Part numbers
Show all part numbers (6)
9029-UC, 9058-UC, 8000-0070, 8000-0110, 8000-0107, 8000-0085
Request a price and lead time
PCI-600 — programmable 10–600 A primary current source for relay testing. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the difference between models 9029-UC and 9058-UC?
The supply voltage. The 9029-UC is ordered for 110 V and the 9058-UC for 220 V.
How is the timer stopped during relay testing?
By a voltage of 24-300 V DC or peak AC, by a dry contact, or by the loss of primary current.
Which devices does the PCI-600 test?
Thermal, electromagnetic and electronic motor protection relays, moulded-case circuit breakers and current transformers.