International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

PCI-600 — programmable 10–600 A primary current source for relay testing

The PCI-600 is a programmable AC current source for substation work. It injects a current from 10 to 600 A, measures it through an isolated current transformer and records the operating time of protective devices.

Type
Programmable AC current source for primary injection
Test current
10–600 A
Built-in ammeter
100 mA – 1000 A, 1 % of reading ±20 mA
Measuring method
Isolated current transformer

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The PCI-600 is mainly used to check protective relays by primary current injection at power utility substations. The same unit tests thermal, electromagnetic and electronic motor protection relays and moulded-case circuit breakers, measures primary and secondary currents of current transformers, and serves other tasks that need a high-current source.

The unit generates an AC test current from 10 to 600 A. The built-in current meter covers 100 mA to 1000 A with an accuracy of 1 % of reading ±20 mA, measured through an isolated current transformer. A separate external current input covers 10 mA to 10 A with an accuracy of 1 % of reading ±2 mA. Results are shown on a backlit four-line display with twenty characters per line.

The built-in timer measures intervals from 1 ms to 2 hours with an accuracy of 0.1 % of reading ±1 ms. The timer can be stopped by a voltage of 24–300 V DC or peak AC, by a dry contact, or by the loss of primary current, which determines the time delay before a protective relay operates.

The supply is 100–120 V AC or 200–240 V AC, 50/60 Hz, and the voltage is set at the factory. Models are ordered as 9029-UC for 110 V or 9058-UC for 220 V. An RS-232C port at 19200 baud is used for factory calibration and diagnostics. The design is built to IEC 61010 (1995), with UL 61010A-1 and CSA-C22.2 also satisfied.

The dimensions are 42.6 x 32.0 x 27 cm and the weight is 21 kg. Operating temperature runs from -10 to 50 °C and storage from -30 to 70 °C, with specifications stated at nominal voltage and +25 °C. The kit includes 10 ft #1/0 AWG test leads, a mains cord and an earth cable. A transport case is available as an option, and the 8000-0070, 8000-0110, 8000-0107 and 8000-0085 cable sets are available separately.

Technical specifications

TypeProgrammable AC current source for primary injection
Test current10–600 A
Built-in ammeter100 mA – 1000 A, 1 % of reading ±20 mA
Measuring methodIsolated current transformer
External current input10 mA – 10 A, 1 % of reading ±2 mA
Timer1 ms – 2 hours, 0.1 % of reading ±1 ms
Timer stop24–300 V DC or peak AC, dry contact, or loss of primary current
DisplayBacklit LCD, 4 lines of 20 characters
Supply100–120 V AC or 200–240 V AC (factory set), 50/60 Hz
InterfaceRS-232C (19200 baud) for calibration and diagnostics
Dimensions42.6 x 32.0 x 27 cm
Weight21 kg
Operating temperature-10 to 50 °C
Storage temperature-30 to 70 °C
SafetyIEC 61010 (1995), with UL 61010A-1 and CSA-C22.2
Supplied with#1/0 AWG leads 10 ft, mains cord, earth cable

Part numbers

Show all part numbers (6)

9029-UC, 9058-UC, 8000-0070, 8000-0110, 8000-0107, 8000-0085

Request a price and lead time

PCI-600 — programmable 10–600 A primary current source for relay testing. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What is the difference between models 9029-UC and 9058-UC?

The supply voltage. The 9029-UC is ordered for 110 V and the 9058-UC for 220 V.

How is the timer stopped during relay testing?

By a voltage of 24-300 V DC or peak AC, by a dry contact, or by the loss of primary current.

Which devices does the PCI-600 test?

Thermal, electromagnetic and electronic motor protection relays, moulded-case circuit breakers and current transformers.