PAD56 — insulation test set, 5 kV AC and 6 kV DC, with megohmmeter up to 1000000 MΩ
The PAD56 applies up to 6 kV DC or 5 kV AC to electrical insulation. It measures the leakage current through insulation to earth and insulation resistance up to 1000000 MΩ.
- Type
- AC/DC insulation test set with megohmmeter
- AC voltage
- 5 kV AC
- DC voltage
- 6 kV DC
- DC leakage current
- 0.01 to 5000 µA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The PAD56 is a portable set for high-voltage insulation testing of electrical equipment, with a built-in megohmmeter. It is used to check insulation in switchgear, cables, motors, transformers and generators, for dielectric withstand and leakage current measurements, as an aid when locating cable faults, and in planned preventive maintenance programmes.
The set produces up to 6 kV DC or up to 5 kV AC on the test object. While the voltage is applied it measures the leakage current through the main insulation to earth, which is effectively a measure of insulation resistance. The DC leakage current is read from the front-panel meter between 0.01 and 5000 µA, and the AC leakage current between 0.1 and 5 mA.
Insulation resistance up to 1000000 MΩ is read directly from the scale at a test voltage of 2.5 kV or 5 kV DC. For other voltages a scale of factors is provided, so the operator recalculates the reading without separate tables. A high upper limit of measurement suits the condition of new or dry insulation in low- and medium-voltage equipment.
The housing is light and sturdy, designed for long-term field use. Analogue needle meters with a clear scale and simple controls let the operator follow the change in current while the voltage rises and is held.
The PAD56 belongs to a range of megohmmeter test sets together with the PAD10-25 (10 kV AC / 25 kV DC) and the PM15-2 (15 kV DC). Within this range it has the lowest voltage and the highest insulation resistance limit, which makes it suitable for lower-voltage equipment and for precise checks of insulation with low leakage current.
Technical specifications
| Type | AC/DC insulation test set with megohmmeter |
|---|---|
| AC voltage | 5 kV AC |
| DC voltage | 6 kV DC |
| DC leakage current | 0.01 to 5000 µA |
| AC leakage current | 0.1 to 5 mA |
| Insulation resistance | Up to 1000000 MΩ |
| Test voltage for resistance | 2.5 kV or 5 kV DC, scale of factors for other values |
| Indication | Analogue needle meters |
| Application | Switchgear, cables, motors, transformers, generators |
Request a price and lead time
PAD56 — insulation test set, 5 kV AC and 6 kV DC, with megohmmeter up to 1000000 MΩ. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What voltage does the PAD56 supply?
Up to 6 kV DC or up to 5 kV AC.
What is the highest insulation resistance that can be measured?
Up to 1000000 MΩ, read directly from the scale at 2.5 kV or 5 kV DC. For other voltages a scale of factors is used.
What are the lowest leakage current readings the set shows?
0.01 µA on DC and 0.1 mA on AC.