PAD10-25 — insulation test set, 10 kV AC and 25 kV DC, with megohmmeter
The PAD10-25 combines an AC and DC test voltage source with a megohmmeter. It carries out dielectric withstand tests, measures leakage current and reads insulation resistance up to 150000 MΩ.
- Type
- AC/DC insulation test set with megohmmeter
- Alternating voltage
- 0–10 kV AC
- Direct voltage
- 0–25 kV DC, negative polarity
- Output current
- Up to 5 mA DC, up to 10 mA AC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The PAD10-25 is a portable set for dielectric withstand testing with AC and DC voltage, for measuring insulation resistance and leakage current, and for measuring large unknown resistances. It is used to check insulation in switchgear, cables, motors, transformers and generators, to help locate cable faults, and in planned preventive maintenance programmes.
The set delivers 0 to 10 kV AC and 0 to 25 kV DC of negative polarity. Its output current reaches up to 5 mA DC and up to 10 mA AC. Leakage current is measured between 0.02 and 5000 µA on DC and between 1 and 10 mA on AC, which allows the condition of the main insulation to be judged against earth.
Insulation resistance is read straight from the scale across four ranges: 0.1 to 5000 MΩ at 500 VDC, 0.5 to 25000 MΩ at 2500 VDC, 1 to 50000 MΩ at 5000 VDC, and 3 to 150000 MΩ at 15000 VDC. For other voltages the resistance is calculated: the voltage reading in kilovolts is divided by the current reading in microamperes and multiplied by 1000.
The housing is light and sturdy, designed for many years of field use. Analogue needle meters with clear scales and simple controls are on the front panel, so the operator can watch both voltage and current while the voltage is raised and held.
The PAD10-25 belongs to a range of megohmmeter test sets alongside the PAD56 (5 kV AC / 6 kV DC) and the PM15-2 (15 kV DC). Of these, the PAD10-25 offers the highest AC voltage and suits testing medium-voltage equipment.
Technical specifications
| Type | AC/DC insulation test set with megohmmeter |
|---|---|
| Alternating voltage | 0–10 kV AC |
| Direct voltage | 0–25 kV DC, negative polarity |
| Output current | Up to 5 mA DC, up to 10 mA AC |
| DC leakage current | 0.02 to 5000 µA |
| AC leakage current | 1 to 10 mA |
| Insulation resistance at 500 VDC | 0.1–5000 MΩ |
| Insulation resistance at 2500 VDC | 0.5–25000 MΩ |
| Insulation resistance at 5000 VDC | 1–50000 MΩ |
| Insulation resistance at 15000 VDC | 3–150000 MΩ |
| Indication | Analogue needle meters |
| Application | Switchgear, cables, motors, transformers, generators |
Request a price and lead time
PAD10-25 — insulation test set, 10 kV AC and 25 kV DC, with megohmmeter. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the highest voltage the PAD10-25 supplies?
Up to 10 kV AC and up to 25 kV DC of negative polarity, with output current up to 10 mA AC and 5 mA DC.
How is insulation resistance read at a voltage without its own scale?
The voltage reading in kilovolts is divided by the current reading in microamperes and multiplied by 1000, giving the result in megohms.
Which model in the range has a lower voltage?
The PAD56 supplies 5 kV AC and 6 kV DC, while the PM15-2 works only on DC at up to 15 kV.