Myrkos 2 — portable gas-in-oil analyser for dissolved gases in transformer oil, 9 gases
The Myrkos 2 analyses gases dissolved in insulating oil on site, with near-laboratory quality. It combines gas chromatography with headspace extraction, in line with ASTM D3612-02 and IEC 60567.
- Analysed gases
- H₂, CO, CO₂, CH₄, C₂H₂, C₂H₄, C₂H₆, O₂, N₂
- Analysis time
- 2 minutes
- Sampling
- ShakeTest syringe, 100 mL, for liquid; glass syringe, 10 mL, for gas from relay or headspace
- Liquids
- Mineral oil, silicone fluid, natural and synthetic esters
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The analyser is used to assess transformer condition in situ, at remote sites, to confirm alarms raised by monitoring systems, for frequent oil checks on ageing transformers, and during recommissioning and commissioning. It is also used in laboratories for DGA work.
Nine gases are measured: H₂, CO, CO₂, CH₄, C₂H₂, C₂H₄, C₂H₆, O₂ and N₂. The unit handles mineral oil, silicone fluid and natural and synthetic esters, and solubility coefficients are stored for each liquid type. Liquid samples are drawn with a 100 mL ShakeTest syringe, while gas samples from a relay or headspace are taken with a 10 mL glass syringe. A single syringe serves for sampling, extraction and measurement, and a result appears two minutes after the sample is introduced.
The control computer has a 14-inch screen and runs PPMreport, which produces customisable reports. The MyrkosView program provides basic diagnostics, including Duval triangles and pentagon, IEC and Rogers ratios, the Key Gas method and condition levels to IEEE C57.104-2008. Data can be exported as CSV and graphs as PNG. On-screen instructions guide sampling and gas extraction, and the interface is available in six languages. Connection is possible directly by TCP/IP or over a network.
Helium carrier gas of 99.999 % purity is supplied at 80 psig, and the helium module is rated for 42 hours of operation between refills. The calibration cylinder is a 920 cc aluminium alloy TALL CALGAS with NIST traceability, which lasts 30 months, and calibration is carried out daily. A lithium-ion battery with a status indicator gives 9 hours of independent operation.
The field kit comes in a waterproof case with wheels and a telescopic handle, with a field module and a case for ShakeTest syringes. The laboratory kit adds a syringe shaker for higher sample throughput. The unit operates from 0 to 50 °C, can be stored from 0 to 75 °C, tolerates 5–95 % humidity without condensation and works up to 4500 m. It is rated IP67 when closed and IP20 when open under IEC 60529, and meets IEC/EN 61010-1 safety and IEC 61326-1 and EN 55011 EMC requirements. The shipping mass is 42 kg (92 lb).
Technical specifications
| Analysed gases | H₂, CO, CO₂, CH₄, C₂H₂, C₂H₄, C₂H₆, O₂, N₂ |
|---|---|
| Analysis time | 2 minutes |
| Sampling | ShakeTest syringe, 100 mL, for liquid; glass syringe, 10 mL, for gas from relay or headspace |
| Liquids | Mineral oil, silicone fluid, natural and synthetic esters |
| Software | PPMreport, MyrkosView |
| Calibration cylinder | TALL CALGAS 920 cc, NIST traceable |
| Carrier gas | Helium 99.999 %, 80 psig; 42 hours of operation |
| Battery | Lithium-ion, 9 hours |
| Connectivity | TCP/IP direct or networked |
| Operating temperature | 0...50 °C |
| Storage temperature | 0...75 °C |
| Humidity | 5–95 % non-condensing |
| Altitude | 0-4500 m (15000 ft) |
| Ingress protection | IP67 when closed, IP20 when open (IEC 60529) |
| Safety | IEC/EN 61010-1 |
| EMC | IEC 61326-1, EN 55011, FCC part 15 Subpart B, ICES-003 |
| Shipping dimensions | 42.0 x 21.5 x 18.75 in |
| Shipping weight | 42 kg (92 lb) |
| Methods | Method C of ASTM D3612-02, and IEC 60567 |
Part numbers
Show all part numbers (2)
Myrkos Field Package, Myrkos Lab Package
Request a price and lead time
Myrkos 2 — portable gas-in-oil analyser for dissolved gases in transformer oil, 9 gases. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which liquids can the Myrkos 2 analyse?
Mineral oil, silicone fluid, and natural and synthetic esters. Solubility coefficients are stored for each type of liquid.
How long can the unit run without mains power?
The lithium-ion battery gives 9 hours of operation, and the helium module lasts 42 hours between refills.
How do the field and laboratory kits differ?
The field kit comes in a waterproof wheeled case with a field module, while the laboratory kit adds a syringe shaker for more analyses.