International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

MTS-5100 relay protection test system with six current and four voltage channels

The MTS-5100 tests and calibrates protection and control relays, simulates power system conditions and checks voltage, current, phase and power transducers. All functions are available from the front panel, with no extra options needed for operation.

AC current outputs
6 x 0–30 A; 3 x 0–60 A; 1 x 0–180 A
DC current output
0–5 A
Voltage outputs
AC 0–250 V three-phase; AC 0–750 V single-phase; DC 0–350 V
Three-phase AC power
85 VA per channel; 900 VA for all three

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The system covers everything from testing a single maximum-current relay to end-to-end tests of multi-terminal schemes. Each output channel has enough power for older electromechanical relays, so fewer reconnections are needed, while the number of current and voltage channels matches what microprocessor relays require. Static tests, dynamic ramp and linear modes, and state sequences are supported, along with playback of transient waveforms in COMTRADE format (IEEE C37.111) and tests synchronised by GPS.

In transmission and distribution networks it covers maximum-current and directional protection, under- and overvoltage protection, distance, frequency and differential protection of lines, transformers and busbars, capacitor bank protection, synchronism check, auto-reclosing, breaker failure, blocking and timing relays. For generators it tests differential protection, loss of excitation, overexcitation, stator earth faults, negative sequence and reverse power. The unit also checks panel meters, the metering functions of digital relays, and recloser controllers with a 14-pin connector.

The system has six current channels for AC and DC: 6 x 30 A, 3 x 60 A or 1 x 180 A AC, and DC of 0 to 5 A. Four voltage channels deliver 0 to 250 V in three-phase mode, 0 to 750 V in single-phase mode and 0 to 350 V DC. Current and voltage accuracy is the greater of 0.15% of setting or 10 mA (10 mV) respectively. Resolution is 0.001 A and 0.01 V, the bandwidth is 3 kHz, and current distortion is below 0.5%, typically below 0.2%.

There are 12 inputs for dry contacts or voltage (±300 V DC, 0 to 225 V AC), four type A contact outputs rated at 5 A / 240 V AC and 0.4 A / 300 V DC, and a transducer input accepting 0 to ±10 V or ±20 mA with a 0.1% of reading error. Other connections include a GPS input with antenna, an IRIG-B input and output, and GOOSE messaging under IEC 61850. The 10.1-inch screen stores results in internal memory or on a USB drive directly from the front panel.

Power is 100 to 240 V AC, drawing up to 1800 VA. The unit weighs 49 lb (22.2 kg) and measures 18.9 by 14.5 by 11.7 inches (48.0 by 36.8 by 29.7 cm). Operating range is -10 to 50 °C, storage -30 to 70 °C, and humidity 5 to 90% non-condensing. Accessories include hard and soft cases, a set of test leads, a foot switch, an RTC14 cable for recloser controllers, a wireless keyboard and a bench trolley for substations.

Technical specifications

AC current outputs6 x 0–30 A; 3 x 0–60 A; 1 x 0–180 A
DC current output0–5 A
Voltage outputsAC 0–250 V three-phase; AC 0–750 V single-phase; DC 0–350 V
Three-phase AC power85 VA per channel; 900 VA for all three
Single-phase AC power250 VA on one channel; 2400 VA on one channel
Current error (above 5% of range)0.15% of setting or 10 mA, whichever is greater
Current resolution0.001 A
Voltage error (above 5% of range)0.15% of setting or 10 mV, whichever is greater
Voltage resolution0.01 V
Bandwidth (-3 dB)3 kHz
Contact outputs4 x type A, 5 A / 240 V AC; 0.4 A / 300 V DC
Contact and voltage inputs12 channels, ±300 V DC, 0 to 225 V AC
Transducer input0 to ±10 V DC or 0 to ±20 mA DC
IRIG-B output5 V TTL, isolated
Power supply100–240 V AC, up to 1800 VA
Weight49 lb (22.2 kg)
Dimensions (W x H x D)18.9 by 14.5 by 11.7 inches (48.0 by 36.8 by 29.7 cm)
Operating temperature-10 to 50 °C
Storage temperature-30 to 70 °C
Protocols and formatsIEC 61850 GOOSE, IEEE C37.111 COMTRADE

Request a price and lead time

MTS-5100 relay protection test system with six current and four voltage channels. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Is the MTS-5100 suitable for electromechanical relays?

Yes. Each current channel has enough power for electromechanical relays, rated 85 VA per channel in three-phase mode and up to 250 VA on one channel in single-phase mode.

Can recorded fault events be replayed?

Yes. The system plays back transient waveforms in COMTRADE format under IEEE C37.111. GPS synchronisation is available for end-to-end tests.

How are recloser controllers tested?

Controllers with a 14-pin connector are tested with the RTC14 cable, which connects without intervention in the circuit.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides