MRM-200-V2 micro-ohmmeter for high current tests, up to 200 A
The MRM-200-V2 is the top model in the MRM series, for measuring resistance of breaker contacts, windings of transformers and motors, cable samples and busbar joints. Its true direct current reaches 200 A, across three ranges from 0.1 µΩ to 1 Ω.
- Model
- MRM-200-V2
- Output current
- 5 A to 200 A, direct current (true DC)
- Measuring ranges
- 0.1 µΩ – 2 mΩ (0.1 µΩ); 2 mΩ – 200 mΩ (10 µΩ); 200 mΩ – 1 Ω (1 mΩ)
- Smallest step
- 0.1 µΩ
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A high test current of up to 200 A is needed where a contact must be checked under conditions closer to working ones, such as on power breakers, disconnectors and busbar joints. The model completes the series alongside the 10 A and 100 A instruments. The case is light and rugged, and the instrument works in the laboratory and on site.
The instrument has three bands: from 0.1 µΩ up to 2 mΩ at 0.1 µΩ resolution, from 2 mΩ up to 200 mΩ at 10 µΩ resolution, and from 200 mΩ up to 1 Ω at 1 mΩ resolution. The basic accuracy is ±1% of reading from 50 µΩ to 1 Ω.
Measurement uses a four-terminal Kelvin circuit, so the resistance of connecting leads does not affect the reading. Control is microprocessor-based and the result is shown on a digital screen. Data is sent to a computer over Bluetooth or USB, and the software includes a report generator. Power supply is 100 to 240 V at 50 or 60 Hz, and the unit meets IEC safety requirements and is calibrated to ISO 17025.
The kit includes two 19 ft (6 m) leads with combined current and voltage circuits, one red and one black, each with a U-tip and an 80 mm clamp. A green 10 ft (3 m) earth lead has a crocodile clip opening 20 mm. A mains cord, a 6 ft (1.8 m) USB cable, the software licence, a user manual and a cable bag are also supplied.
Optional leads with U-tips and clamps, 170 mm long and opening to 41 mm, can be ordered separately. For 200 A they come in 6, 8, 10, 12 and 15 m lengths, and for 100 A also in 3 m.
Technical specifications
| Model | MRM-200-V2 |
|---|---|
| Output current | 5 A to 200 A, direct current (true DC) |
| Measuring ranges | 0.1 µΩ – 2 mΩ (0.1 µΩ); 2 mΩ – 200 mΩ (10 µΩ); 200 mΩ – 1 Ω (1 mΩ) |
| Smallest step | 0.1 µΩ |
| Basic accuracy | ±1% of reading in the 50 µΩ – 1 Ω range |
| Power supply | 100 to 240 V at 50 or 60 Hz |
| Measurement principle | four-terminal Kelvin circuit |
| Control | microprocessor-based |
| Interfaces | Bluetooth, USB |
| Safety | complies with IEC safety requirements |
| Calibration | ISO 17025 |
| Test leads | 19 ft (6 m), clamp opening 80 mm |
Request a price and lead time
MRM-200-V2 micro-ohmmeter for high current tests, up to 200 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the upper resistance limit of the MRM-200-V2?
It measures up to 1 Ω in the third range, which has 1 mΩ resolution. Basic accuracy is ±1% of reading from 50 µΩ to 1 Ω.
Which lead lengths are available for 200 A?
Optional leads for 200 A come in 6, 8, 10, 12 and 15 m lengths, and the standard kit includes 6 m leads.
How are results transferred?
Over Bluetooth or USB to a computer, where the software produces a report.
Similar equipment from other manufacturers