International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

MRM-100-V2 micro-ohmmeter for very low contact resistance, up to 100 A

The MRM-100-V2 measures very low resistances of switch and breaker contacts, windings of transformers and motors, wire and cable samples and busbar joints. Output is true direct current from 5 A upward to 100 A, and resolution reaches 0.1 µΩ.

Model
MRM-100-V2
Output current
5 to 100 A, true DC
Measuring ranges
0.1 µΩ up to 2 mΩ, 0.1 µΩ steps; 2 mΩ up to 300 mΩ, 10 µΩ steps
Resolution
down to 0.1 µΩ

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The MRM series includes models rated at 10, 100 and 200 A. The 100 A version has built-in memory and a printer, and its two-sided earth circuit suits substation tests where the equipment is earthed at both ends. The case is light and rugged, and measurements can be taken in the laboratory or on site.

Measurement uses a four-terminal Kelvin circuit, so the current and voltage leads are separated and the resistance of the leads does not enter the result. Control is microprocessor-based, with a digital display. Data goes to a computer over Bluetooth or USB, and the control software includes a report generator.

Two resistance ranges are provided. The lower band runs from 0.1 µΩ to 2 mΩ, stepping by 0.1 µΩ, and the upper band from 2 mΩ to 300 mΩ, stepping by 10 µΩ. The basic accuracy is ±1% of reading in the 50 µΩ to 300 mΩ range. Power supply is 100 to 240 V at 50 or 60 Hz, and the unit meets IEC safety requirements and is calibrated to ISO 17025.

The kit includes two 19 ft (6 m) test leads with combined current and voltage circuits, one red and one black, each with a U-shaped tip and a clamp opening of 80 mm. A separate green 10 ft (3 m) earth lead has a U-tip and a crocodile clip opening 20 mm. A mains cord, a 6 ft (1.8 m) USB cable, the software licence, a user manual and a cable bag are also supplied.

Longer leads with U-tips and clamps are available to order, opening up to 41 mm for the 170 mm length. For 100 A, these leads come in 3, 6, 8, 10, 12 and 15 m lengths, and for 200 A in lengths from 6 to 15 m.

Technical specifications

ModelMRM-100-V2
Output current5 to 100 A, true DC
Measuring ranges0.1 µΩ up to 2 mΩ, 0.1 µΩ steps; 2 mΩ up to 300 mΩ, 10 µΩ steps
Resolutiondown to 0.1 µΩ
Basic accuracy±1% of reading in the 50 µΩ – 300 mΩ range
Power supply100 to 240 V at 50 or 60 Hz
Measurement principlefour-terminal Kelvin circuit
Controlmicroprocessor-based
InterfacesBluetooth, USB
Safetycomplies with IEC safety requirements
CalibrationISO 17025
Test leads19 ft (6 m), clamp opening 80 mm

Request a price and lead time

MRM-100-V2 micro-ohmmeter for very low contact resistance, up to 100 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How accurate is the MRM-100-V2 on very low resistances?

Basic accuracy is ±1% of reading in the 50 µΩ to 300 mΩ range. Resolution is 0.1 µΩ up to 2 mΩ.

Is the unit suitable for substations earthed on both sides?

Yes, the 100 A model has a two-sided earth circuit for substation tests where the equipment is earthed at both ends.

What leads come with the kit?

A pair of 6 m leads with a U-tip and an 80 mm clamp, and a green 3 m earth lead with a 20 mm crocodile clip. Longer leads up to 15 m are available to order.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides