MCCB-250 moulded-case circuit breaker tester, 250 A
The MCCB-250 is a programmable high-current source for testing moulded-case circuit breakers, as well as thermal, magnetic and electronic overload relays for motors. A built-in timer measures tripping times.
- Type
- 250 A current source
- Output currents
- 0–5 A at 120 V; 0–25 A at 24 V; 0–120 A at 6 V; 0–250 A at 3 V
- Instantaneous current
- 700 A
- Internal current meter
- 100 mA – 1000 A, 1% of reading ±20 mA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The unit has four current source outputs: 0 to 5 A at 120 V, 0 to 25 A at 24 V, 0 to 120 A at 6 V and 0 to 250 A at 3 V AC. Current flows through load circuits of high impedance. Each output tolerates short overloads, which is used to test the instantaneous trip, where the current reaches 700 A. For 100% of rated current the on-time is up to 30 minutes with a 30-minute pause, for 200% up to 3 minutes with a 5-minute pause, and for 300% up to 30 seconds with a 4-minute pause.
The source and timer switch on together at the next zero crossing once a test starts. The timer stops on a 24 to 300 V DC or peak AC signal, on a dry contact, or when the test current disappears. Results appear in milliseconds and fractions of a cycle on a backlit LCD with four lines of 20 characters, readable in bright sunlight and in dim light.
The internal current meter works through an isolated current transformer, covering 100 mA to 1000 A with an error of 1% of reading plus or minus 20 mA. An external 0 to 10 A input (10 mA to 10 A, 1% of reading plus 2 mA) shows current alongside the internal meter. The timer ranges from 1 ms to 2 hours with 0.1% of reading plus 1 ms accuracy, and an RS-232C port serves factory calibration and diagnostics.
Supply is 100 to 120 V or 200 to 240 V AC at 50 or 60 Hz, set at the factory. Dimensions are 16.8 by 12.6 by 10.6 inches (42.6 by 32.0 by 27.0 cm) and the weight is 46 lb (21 kg). The enclosure is rated IP32 with pollution degree 2 and must run with the lid open for ventilation. The design follows IEC 61010 (1995), UL 61010A-1 and CSA C22.2. Operating range is -10 to 50 °C, storage is -30 to 70 °C, humidity up to 90% at 40 °C non-condensing, and altitude up to 2000 m.
Only trained operators should work with the unit, and the breaker under test must be taken out of service and fully isolated. The kit includes a mains cord, an earth cable and 10 ft test leads of #2 AWG, and a transport case is available as an option. Model 9066-UC is built for 110 V and 9067-UC for 220 V.
Technical specifications
| Type | 250 A current source |
|---|---|
| Output currents | 0–5 A at 120 V; 0–25 A at 24 V; 0–120 A at 6 V; 0–250 A at 3 V |
| Instantaneous current | 700 A |
| Internal current meter | 100 mA – 1000 A, 1% of reading ±20 mA |
| Measurement method | isolated current transformer |
| External meter | 10 mA – 10 A, 1% of reading ±2 mA |
| Timer range | 1 ms – 2 hours, 0.1% of reading ±1 ms |
| Timer stop inputs | 24–300 V DC or peak AC voltage, dry contact, loss of current |
| Display | backlit LCD, 20 characters by 4 lines |
| Interface | RS-232C |
| Power supply | 100–120 V or 200–240 V AC, 50/60 Hz |
| Dimensions | 16.8 by 12.6 by 10.6 inches (42.6 by 32.0 by 27.0 cm) |
| Weight | 46 lb (21 kg) |
| Protection rating | IP32 |
| Operating temperature | -10 to 50 °C |
| Storage temperature | -30 to 70 °C |
| Safety | IEC 61010 (1995), UL 61010A-1, CSA C22.2 |
Part numbers
Show all part numbers (7)
9066-UC, 9067-UC, 9066-SC, 8000-0016, 8000-0086, 8000-0089, 8000-0090
Request a price and lead time
MCCB-250 moulded-case circuit breaker tester, 250 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the 9066-UC and 9067-UC versions differ?
9066-UC is designed for a 110 V supply and 9067-UC for 220 V. Both are supplied with the unit and its cables.
How is the instantaneous element of a breaker tested?
The outputs tolerate short overloads, so the instantaneous current reaches 700 A. For 300% of rated current, the on-time is up to 30 seconds.
Which cables are available for the MCCB-250?
A combined power and earth cable 8000-0016, a 10 ft #4 AWG current cable kit 8000-0086, a #10 AWG current cable 8000-0089, and a timer and measurement cable kit 8000-0090.