M4100 power factor and capacitance test set for high voltage insulation, 12 kV
The fourth-generation M4100 measures power factor (tan delta) and insulation capacitance during commissioning, diagnostic work and scheduled testing. Its 3 kVA source delivers up to 12 kV AC, and the unit is controlled from a PC.
- Test voltage
- from 25 V up to 12 kV AC
- Source rating
- 3 kVA
- Output current at 10 kV
- 100 mA continuous; 200 mA for 30 min; 300 mA for 4 min
- PF / tan delta range
- 0 to ±100.00%; 0 to ±1.0000
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The M4100 is used to assess the insulation of power transformers, bushings, circuit breakers, capacitor banks and other high voltage equipment. Its main measurements are power factor and tan delta to check insulation quality, capacitance to detect physical changes in the asset, turns ratio to locate shorted turns, leakage reactance (short-circuit impedance) to judge winding distortion, single-phase excitation current, and testing of individual capacitors within a bank.
A built-in generator produces a clean test signal. A patented mains frequency modulation technique measures at frequencies above and below the system frequency and removes the effect of varying electrostatic interference in the substation. Firmware monitors abnormal current, temperature and voltage. For safety the unit has protective switches, strobe lights and interlocks tied to a ground monitoring relay.
The source is rated 3 kVA with a range of 25 V to 12 kV. Output current at 10 kV is 100 mA continuous, 200 mA for 30 minutes and 300 mA for 4 minutes. Measuring ranges are capacitance 0 to 100 µF, inductance 6 H to 10 MH, and real power 0 to 2 kW.
Extensions include the M4110 interface for measuring leakage reactance, and the M4140 kit for testing capacitors without disconnecting them from the bank, which requires the M4110. Also available are the built-in M4151 field calibration module, a Type C resonant reactor for assets with high charging current, a TTR capacitor rated up to 10 kV for turns ratio testing at high voltage, and the M4300 trolley for transport.
The unit is controlled from a laptop or tablet over USB or a serial port using the DTA software, which contains standard test procedures and keeps a results database. It runs from 95 to 264 VAC with automatic voltage selection at 47 to 63 Hz, works from -20 to 50 °C, and weighs 43 kg. It measures 26 by 50.8 by 64.1 cm and complies with EN 61010-1, EN 61326 and the IEC 61000-4 series.
Technical specifications
| Test voltage | from 25 V up to 12 kV AC |
|---|---|
| Source rating | 3 kVA |
| Output current at 10 kV | 100 mA continuous; 200 mA for 30 min; 300 mA for 4 min |
| PF / tan delta range | 0 to ±100.00%; 0 to ±1.0000 |
| Capacitance | 0 – 100 µF |
| Inductance | 6 H – 10 MH |
| Real power | 0 – 2 kW |
| Power supply | 95-264 VAC, automatic detection; 47–63 Hz |
| Operating temperature | -20 … 50 °C |
| Weight | 43 kg (95 lb) |
| Dimensions | 26 by 50.8 by 64.1 cm |
| PC interface | USB or serial port |
| Standards | EN 61010-1, EN 61326, IEC 61000-4 immunity parts 2 to 6 and 11 |
Part numbers
Show all part numbers (2)
M4K60, M4K100
Request a price and lead time
M4100 power factor and capacitance test set for high voltage insulation, 12 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the difference between M4K60 and M4K100?
The M4K60 kit includes cables, a strobe, a temperature and humidity sensor, two safety switches, DTA6 Basic software, the M4151 module and a 65 ft high-voltage cable. The M4K100 has the same content with a 100 ft cable.
Can the short-circuit impedance of a transformer be measured?
Yes, with the M4110 interface, which the test requires. The M4110 is also needed for the M4140 kit that checks capacitor banks.
How does the unit cope with strong interference in a substation?
A patented mains frequency modulation technique measures at frequencies above and below the system frequency. This removes the effect of varying electrostatic interference.