International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

Line Post Current and Voltage Sensors for 15, 27 and 35 kV Lines, LEA Output

These sensors are mounted on pole structures of 15, 27 and 35 kV overhead lines in place of line insulators. They measure voltage, current or both, and output a low-voltage analogue LEA signal proportional to the primary quantity for distribution automation controllers.

Type
line post current and voltage sensor
Voltage classes
15 kV, 27 kV, 35 kV
Variants
CMI (current), VMI (voltage), CVMI (current and voltage)
Current ratio
600A:10V, 1000A:10V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Line post sensors are intended for outdoor installation on poles and structures of 15 kV, 27 kV and 35 kV overhead lines. Each unit takes the place of a conventional line insulator while also measuring voltage, current or both. Their output feeds smart grid controllers, reclosers and metering systems, which use the signal to supervise the network.

The range is split into three types. The CMI variant measures current only, with a ratio of 600A:10V or 1000A:10V. The VMI variant measures voltage only, with ratios of 1400:1 or 10000:1 at 15 kV, 2200:1 or 10000:1 at 27 kV, and 3300:1 or 10000:1 at 35 kV. The CVMI variant combines current measurement at 600A:10V with voltage measurement using the same ratios. Other current and voltage ratios can be made to order.

The housing is moulded from cycloaliphatic epoxy, CEP. The manufacturer cites an extended creepage length for heavily polluted areas, improved dielectric performance, and a greater striking distance to withstand lightning impulses. Current measurement uses a twin-core inductive circuit with high accuracy and full phase-shift compensation. The low energy analogue outputs are safer than the secondary circuits of conventional current transformers.

The sensor is lightweight and offers rated mechanical strength. Installation can be carried out without de-energising the line and without cutting the conductor: the conductor is laid into a clamped groove and secured with a swing style keeper. Mounting uses a centre pin or a 3 inch bolt circle, and earthing is made through a separate plate.

The sensors work with most existing and new controllers. Connection uses cables with a 2-pin (PSC820221XX) or 4-pin (PSC820211XX) MIL-DTL-5015 military grade connector, and cables of other configurations are made to order. When selecting a unit, state the voltage class, the measurement type, the ratios and the cable length to the controller.

Technical specifications

Typeline post current and voltage sensor
Voltage classes15 kV, 27 kV, 35 kV
VariantsCMI (current), VMI (voltage), CVMI (current and voltage)
Current ratio600A:10V, 1000A:10V
Voltage ratio 15 kV1400:1, 10000:1
Voltage ratio 27 kV2200:1, 10000:1
Voltage ratio 35 kV3300:1, 10000:1
OutputLow Energy Analog Outputs (LEA)
Housing materialCycloaliphatic Epoxy (CEP)
Mountingcentre pin, 3 inch bolt circle
Conductor retentionclamped groove, swing style keeper
Cable connector2-PIN or 4-PIN, MIL-DTL-5015
CablesPSC820221XX (2 PIN), PSC820211XX (4 PIN)

Part numbers

Show all part numbers (18)

PSC82011100, PSC82011200, PSC82012100, PSC82012200, PSC82014100, PSC82014200, PSC82011020, PSC82011010, PSC82012030, PSC82012010, PSC82014040, PSC82014010, PSC82011120, PSC82011110, PSC82012130, PSC82012110, PSC82014140, PSC82014110

Request a price and lead time

Line Post Current and Voltage Sensors for 15, 27 and 35 kV Lines, LEA Output. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does the line need to be de-energised for installation?

No. The manufacturer specifies installation without removing voltage and without cutting the main conductor. The conductor is placed in a clamped groove and secured with a swing style keeper.

Which voltage ratios are available for 27 kV?

The standard ratios for the 27 kV class are 2200:1 and 10000:1. Other ratios are made to order.

What signal does the controller receive?

The sensor outputs a low energy analogue signal (LEA) proportional to the primary voltage or current, for example 10 V at 600 A for the 600A:10V ratio. The connection runs through a cable with a 2-pin or 4-pin MIL-DTL-5015 connector.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides