Line Post Current and Voltage Sensors for 15, 27 and 35 kV Lines, LEA Output
These sensors are mounted on pole structures of 15, 27 and 35 kV overhead lines in place of line insulators. They measure voltage, current or both, and output a low-voltage analogue LEA signal proportional to the primary quantity for distribution automation controllers.
- Type
- line post current and voltage sensor
- Voltage classes
- 15 kV, 27 kV, 35 kV
- Variants
- CMI (current), VMI (voltage), CVMI (current and voltage)
- Current ratio
- 600A:10V, 1000A:10V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Line post sensors are intended for outdoor installation on poles and structures of 15 kV, 27 kV and 35 kV overhead lines. Each unit takes the place of a conventional line insulator while also measuring voltage, current or both. Their output feeds smart grid controllers, reclosers and metering systems, which use the signal to supervise the network.
The range is split into three types. The CMI variant measures current only, with a ratio of 600A:10V or 1000A:10V. The VMI variant measures voltage only, with ratios of 1400:1 or 10000:1 at 15 kV, 2200:1 or 10000:1 at 27 kV, and 3300:1 or 10000:1 at 35 kV. The CVMI variant combines current measurement at 600A:10V with voltage measurement using the same ratios. Other current and voltage ratios can be made to order.
The housing is moulded from cycloaliphatic epoxy, CEP. The manufacturer cites an extended creepage length for heavily polluted areas, improved dielectric performance, and a greater striking distance to withstand lightning impulses. Current measurement uses a twin-core inductive circuit with high accuracy and full phase-shift compensation. The low energy analogue outputs are safer than the secondary circuits of conventional current transformers.
The sensor is lightweight and offers rated mechanical strength. Installation can be carried out without de-energising the line and without cutting the conductor: the conductor is laid into a clamped groove and secured with a swing style keeper. Mounting uses a centre pin or a 3 inch bolt circle, and earthing is made through a separate plate.
The sensors work with most existing and new controllers. Connection uses cables with a 2-pin (PSC820221XX) or 4-pin (PSC820211XX) MIL-DTL-5015 military grade connector, and cables of other configurations are made to order. When selecting a unit, state the voltage class, the measurement type, the ratios and the cable length to the controller.
Technical specifications
| Type | line post current and voltage sensor |
|---|---|
| Voltage classes | 15 kV, 27 kV, 35 kV |
| Variants | CMI (current), VMI (voltage), CVMI (current and voltage) |
| Current ratio | 600A:10V, 1000A:10V |
| Voltage ratio 15 kV | 1400:1, 10000:1 |
| Voltage ratio 27 kV | 2200:1, 10000:1 |
| Voltage ratio 35 kV | 3300:1, 10000:1 |
| Output | Low Energy Analog Outputs (LEA) |
| Housing material | Cycloaliphatic Epoxy (CEP) |
| Mounting | centre pin, 3 inch bolt circle |
| Conductor retention | clamped groove, swing style keeper |
| Cable connector | 2-PIN or 4-PIN, MIL-DTL-5015 |
| Cables | PSC820221XX (2 PIN), PSC820211XX (4 PIN) |
Part numbers
Show all part numbers (18)
PSC82011100, PSC82011200, PSC82012100, PSC82012200, PSC82014100, PSC82014200, PSC82011020, PSC82011010, PSC82012030, PSC82012010, PSC82014040, PSC82014010, PSC82011120, PSC82011110, PSC82012130, PSC82012110, PSC82014140, PSC82014110
Request a price and lead time
Line Post Current and Voltage Sensors for 15, 27 and 35 kV Lines, LEA Output. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the line need to be de-energised for installation?
No. The manufacturer specifies installation without removing voltage and without cutting the main conductor. The conductor is placed in a clamped groove and secured with a swing style keeper.
Which voltage ratios are available for 27 kV?
The standard ratios for the 27 kV class are 2200:1 and 10000:1. Other ratios are made to order.
What signal does the controller receive?
The sensor outputs a low energy analogue signal (LEA) proportional to the primary voltage or current, for example 10 V at 600 A for the 600A:10V ratio. The connection runs through a cable with a 2-pin or 4-pin MIL-DTL-5015 connector.
Similar equipment from other manufacturers