LD60, LD75 and LD100 Liquid Dielectric Test Sets with Test Cells
Semi-automatic LD sets find the breakdown voltage of insulating liquids in transformers, capacitors and bushings. Fitted with the right oil vessel cell, they run tests to ASTM D877, ASTM D1816, IEC 60156, BS 148 and VDE 0370.
- Models
- LD60, LD75, LD100
- Rated voltage
- 60 kV, 75 kV and 100 kV
- Operating mode
- semi-automatic
- Test standards
- ASTM D877, ASTM D1816, IEC 60156, BS 148 and VDE 0370
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The LD range suits quality control of transformer oil and other insulating liquids, whether in a laboratory or out on site. The casing is light yet tough, so the sets stand up to regular use in the field as well as on the bench. The sample goes into a test cell chosen for the standard you need: TC/DE, TC/VDE, TC/IEC or TC/BS.
Three standard models are rated for 60 kV, 75 kV or 100 kV, designated LD60, LD75 and LD100. The controls are grouped on the front panel, with a large digital voltmeter, a power switch with indicator lamp, a rate of rise selector and a start and reset button. The high voltage transformer has a centre tap.
Testing is semi-automatic. Once the cell is seated on the contacts in the test compartment, you select the rate of rise, close the lid and move the switch to start. The voltage then climbs by itself. At breakdown a failure lamp lights and the memory voltmeter holds the reading.
Several features protect the operator: a cover interlock that cuts the circuit when the lid is open, a fast relay that switches off at flashover, a zero start interlock and fuses on the input and the transformer primary. A socket in the compartment takes a motor-driven stirrer for ASTM D1816 and VDE work. The sets run at 10-40°C indoors or outdoors in fair weather, with humidity up to 95%, non-condensing, and altitudes below 3300 ft (1000 metres).
To check the built-in voltmeter, fit the LDCU comparison unit in place of the test cell, either before a test or periodically as a reference. It contains precision voltage dividers and a passive analogue voltmeter, and its brass terminals connect straight to the LD set.
Technical specifications
| Models | LD60, LD75, LD100 |
|---|---|
| Rated voltage | 60 kV, 75 kV and 100 kV |
| Operating mode | semi-automatic |
| Test standards | ASTM D877, ASTM D1816, IEC 60156, BS 148 and VDE 0370 |
| Cell types | TC/DE, TC/VDE, TC/IEC, TC/BS |
| Indication | digital voltmeter with breakdown voltage memory |
| Protection | lid interlock, fast-acting relay, zero start interlock, fuses |
| Working temperature | from 10 to 40°C |
| Humidity | up to 95%, non-condensing |
| Altitude | up to 3300 ft (1000 metres) |
| Applications | transformers, capacitors, bushings, high voltage equipment |
Part numbers
Show all part numbers (4)
LD60, LD75, LD100, LDCU
Request a price and lead time
LD60, LD75 and LD100 Liquid Dielectric Test Sets with Test Cells. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the LD60, LD75 and LD100 models differ?
They differ in rated voltage, which is 60 kV, 75 kV and 100 kV respectively. Controls, protection and the test sequence are the same on all three.
Which standards can the set cover?
With the matching oil vessel test cell, tests follow ASTM D877, ASTM D1816, IEC 60156, BS 148 and VDE 0370. A socket for a motor-driven stirrer is provided for ASTM D1816 and VDE.
How can the voltmeter reading be checked?
Fit the LDCU comparison unit in the test cell position. It has precision dividers and a passive analogue voltmeter, and its reading is compared with the LD set's own voltmeter.