JT-200 — tester for temporary grounding jumpers, 0-3 V output, 200 A

The JT-200 checks temporary grounding jumpers fitted to de-energised power lines and equipment, following ASTM Standard 2249-20E1. Separate voltage sensing leads stop the transition resistance at the connections from distorting the reading.

Input
120 V AC, 60 Hz, single phase, 5 A
Output
0-3 V AC, 200 A
Meter type
3½ digit, 1 % of reading ±5 digits
Voltmeter range
0-3 V AC

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The tester is light and portable, so it suits both field work and workshop use. A current of up to 200 A is passed through the jumper while the instrument measures the voltage drop across it. Dedicated voltage sensing leads are connected directly to the jumper, so the transition resistance between the tester and the object does not distort the result.

Assessment of a jumper's condition is made against voltage tables drawn up from ASTM Standard 2249-20E1 values and Terman's formula for loop inductance. More complex jumper assemblies can also be tested: if the voltage drop across them at 200 A is known, that value is added to the figure taken from the table.

The unit runs from a single-phase 120 V AC, 60 Hz supply and draws 5 A. Its output is 0-3 V AC at 200 A. Digital meters with 3½ digits and an accuracy of 1 % of reading ±5 digits show the readings, with the voltmeter covering 0-3 V AC and the ammeter 0-200 A AC.

The design includes a main supply circuit breaker, start and stop push buttons, and a backup circuit breaker to protect the regulator and transformer. A start-from-zero interlock prevents current being applied while the regulator is not at its zero position. The output is brought out to terminals that carry the voltage sensing leads.

The housing measures 20.5 x 17 x 9 inches (521 x 432 x 229 mm) and weighs 45 lb (20 kg). It is built for prolonged use, and setup is simple. An operation and maintenance manual is supplied with each unit.

Technical specifications

Input120 V AC, 60 Hz, single phase, 5 A
Output0-3 V AC, 200 A
Meter type3½ digit, 1 % of reading ±5 digits
Voltmeter range0-3 V AC
Ammeter range0-200 A AC
Length20.5 in (521 mm)
Width17 in (432 mm)
Height9 in (229 mm)
Weight45 lb (20 kg)
StandardASTM Standard 2249-20E1

Request a price and lead time

JT-200 — tester for temporary grounding jumpers, 0-3 V output, 200 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Why does the tester have separate voltage sensing leads?

They connect directly to the jumper, so the transition resistance between the tester and the jumper does not affect the result.

Can a non-standard jumper assembly be tested?

Yes, provided the voltage drop across the assembly at 200 A is known. That value is added to the figure from the voltage table.

What supply does the JT-200 need?

A single-phase 120 V AC, 60 Hz supply, drawing 5 A.