Hot stick tester for insulated switch sticks, up to 75 kV per 305 mm section, 1 to 6 positions

The hot stick tester checks the dielectric strength of switch sticks and live-line tools. Items are tested at a voltage above their maximum working level, to confirm they will withstand electrical stress in service.

Purpose
testing switch sticks and live-line tools
Number of positions
1 to 6
Maximum length of switch sticks
up to 14 ft (4.24 m)
Other stick length
up to 21 ft (6.4 m)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The hot stick tester belongs to a range of systems for testing electrical protective equipment. It checks switch sticks up to 14 ft (4.24 m) long and other sticks up to 21 ft (6.4 m) long. The maximum test voltage is 75 kV per 12 in (305 mm) section.

The system is made for 1 to 6 test positions, and its size depends on the number of positions. The chamber is reached through large transparent double leaf doors. Several test stations can be fed from one power unit, with each station connected through an optically isolated control network.

The power unit contains a high voltage transformer, a regulator and a control panel. One unit can feed several test modules through an optional high voltage switch, and two units can be combined to double the number of simultaneous tests. Depending on the standard, the set is equipped with an AC source, a DC source or both.

The control panel has a touch screen operator interface with a programmable logic controller. A test is started by a button using pre-programmed parameters, and the operator sees the result and receives a message about a breakdown at a specific position. Results are exported to a computer, and reports are produced by the WINRGTS software. The set complies with current IEC and ASTM standards.

The cabinets are made of 12-gauge cold rolled steel, primed and finished with two coats of urethane paint. All doors have electrical interlocks, so the supply switches off if a door is opened during a test. Exhaust fans rated at 1100 CFM with direct air intake remove ozone. The modular design allows the chambers to be placed apart from the power unit, in line or in an L shape.

Technical specifications

Purposetesting switch sticks and live-line tools
Number of positions1 to 6
Maximum length of switch sticksup to 14 ft (4.24 m)
Other stick lengthup to 21 ft (6.4 m)
Maximum voltage75 kV per 12 in (305 mm) section
Voltage typeAC, DC or AC/DC
Controlstouch screen operator interface and PLC
Reporting softwareWINRGTS
Cabinet12-gauge cold rolled steel, urethane paint
Ozone removal1100 CFM exhaust fans
StandardsIEC, ASTM

Request a price and lead time

Hot stick tester for insulated switch sticks, up to 75 kV per 305 mm section, 1 to 6 positions. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What stick lengths can be tested?

Switch sticks up to 14 ft (4.24 m) and other sticks up to 21 ft (6.4 m), at up to 75 kV per 12 in (305 mm) section.

How many sticks can be tested at the same time?

The set is built for 1 to 6 test positions. Two power units can be combined to double the number of simultaneous tests.

How is the operator protected?

All doors have electrical interlocks that switch off the supply if a door is opened during a test. The stations are connected through an optically isolated control network, and 1100 CFM exhaust fans remove ozone.