HFCT high frequency current transformer clamp for partial discharge, bores of 30, 50 and 70 mm
The HFCT is a split high frequency current transformer that works as an inductive partial discharge sensor. It is clamped around the earth connection of a cable, transformer or machine, and measurements can be made on energised or de-energised equipment.
- Type
- inductive PD sensor
- Bore diameter
- Φ 30 mm, Φ 50 mm, Φ 70 mm
- Bandwidth
- 1 MHz to 60 MHz (30 and 50 mm), 1 MHz to 80 MHz (70 mm)
- Maximum sensitivity (Vout/Iin at 42 MHz, 50 Ω)
- 17 mV/mA (30 and 50 mm), 12 mV/mA (70 mm)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
HFCT sensors are used for insulation diagnostics on medium and high voltage cables, power transformers, rotating machines, GIS, and switchgear of medium and low voltage. Measurements can be taken on equipment under operating voltage (online), or on de-energised equipment during tests (offline).
The sensor encloses the earthing conductor of the object and responds to the high frequency current pulses that accompany partial discharge. The output is a BNC connector, and the signal travels over coaxial cable to the PD acquisition and analysis unit. An arrow on the housing shows the direction of the output voltage Vout relative to the input current Iin, so when the arrow points towards the earth point, Vout is in phase with Iin.
Versions are made for bore diameters of 30, 50 and 70 mm. The 30 and 50 mm versions have a bandwidth of 1 MHz to 60 MHz and a maximum sensitivity of 17 mV/mA, while the 70 mm version covers 1 MHz to 80 MHz at 12 mV/mA. Sensitivity is quoted at 42 MHz into a 50 Ω load.
The 30 mm version is rated for 25 kV peak insulation for one hour. Its output without load is 0.6 Vpp at 100 A and 50 Hz, or 0.4 Vpp for a 100 pC discharge. The 50 mm version withstands 150 A at 50/60 Hz, a 72.5 kV lightning impulse and 15 kV power frequency for one minute, and has IP 58 protection.
Operating temperature for all sizes is -20°C to +70°C. The sensor needs no maintenance, and installation consists of fitting it on the earthing conductor and connecting the cable to the measuring unit.
Technical specifications
| Type | inductive PD sensor |
|---|---|
| Bore diameter | Φ 30 mm, Φ 50 mm, Φ 70 mm |
| Bandwidth | 1 MHz to 60 MHz (30 and 50 mm), 1 MHz to 80 MHz (70 mm) |
| Maximum sensitivity (Vout/Iin at 42 MHz, 50 Ω) | 17 mV/mA (30 and 50 mm), 12 mV/mA (70 mm) |
| Load impedance | 50 Ω |
| Vout without load at 50 Hz (30 mm) | 0.6 Vpp at 100 A |
| Vout without load at PD frequency (30 mm) | 0.4 Vpp at 100 pC |
| Electrical insulation (30 mm) | 25 kV peak for 1 hour |
| Maximum current 50/60 Hz (50 mm) | 150 A |
| Lightning impulse (50 mm) | 72.5 kV |
| Power frequency withstand (50 mm) | 15 kV for 1 min |
| Protection class (50 mm) | IP 58 |
| Output | BNC, coaxial cable |
| Operating temperature | -20 °C to +70 °C |
Part numbers
Show all part numbers (3)
HFCT 30mm, HFCT 50mm, HFCT 70mm
Request a price and lead time
HFCT high frequency current transformer clamp for partial discharge, bores of 30, 50 and 70 mm. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Where is the HFCT fitted?
On the earth connection of the object, such as a cable line, transformer or machine, with the arrow pointing towards the earth point so that Vout is in phase with Iin.
How do the 30, 50 and 70 mm versions differ?
By bore diameter, bandwidth and sensitivity. The 30 and 50 mm versions cover 1 MHz to 60 MHz at 17 mV/mA, while the 70 mm version covers up to 80 MHz at 12 mV/mA. The 50 mm version withstands 150 A and has IP 58 protection.
Can PD be measured without taking the equipment out of service?
Yes. The sensor works both online, under operating voltage, and offline on de-energised equipment, with the signal taken from the BNC output.