HC-12C to HC-75C High Current Test Sets, 12000-75000 A
The HC-C series checks low voltage moulded-case breakers and direct-acting breakers in metal-clad AC switchgear by simulating overload and short-circuit conditions. Four models give maximum currents from 12000 to 75000 A, with automated tests and current waveform display.
- Maximum current HC-12C
- 12000 A
- Maximum current HC-20C
- 20000 A
- Maximum current HC-40C
- 40000 A
- Maximum current HC-75C
- 75000 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Almost any low voltage AC moulded-case breaker, or direct-acting breaker in a metal-clad enclosure, can be tested with these sets by simulating overload and short-circuit conditions. They also check current transformers, thermal and magnetic motor overload relays and ground fault trip devices. In a series configuration the sets serve substation maintenance and primary injection testing of high voltage breakers and protection schemes. All models can be transported for work on site.
Output is adjusted smoothly across the full range by a motorised vernier and a programmable tap switch, which supports automatic pulses and current holding. The power section uses SCR thyristors under programmable phase control, so the current pulses are repeatable with minimal distortion. The measuring circuit switches between current control and contact control.
Five operating modes are available. Normal leaves every function under manual control. Jog-to-Hold pulses according to the Jog on Cycles and Jog off Secs settings and raises the current to the Hold Amps value. Jog-to-Trip pulses until the breaker trips. Current Hold keeps the current within 1% of Hold Amps, while Memory, used to check the sensitivity of electronic trip units, shows the current level once the stop button is pressed.
A digital AC voltmeter monitors input, output and external voltage up to 600 VAC, and the ammeter is accurate to 0.8% of reading plus 0.3% of range. The instruments are calibrated against standards certified by NIST. Computer control is handled by the WIN HC program, which provides menus, a database for repeating and recalling tests, report generation and current waveform display.
Protection includes a circuit breaker, a control power switch with indicator, Output On and open interlock indicators and an emergency stop button. Contact devices HCSS1 and HCSS2 come as standard, and others are supplied as options. Calibration to ISO17025 is available on request.
Technical specifications
| Maximum current HC-12C | 12000 A |
|---|---|
| Maximum current HC-20C | 20000 A |
| Maximum current HC-40C | 40000 A |
| Maximum current HC-75C | 75000 A |
| Output regulation | smooth, motorised vernier and programmable tap switch |
| Power section | SCR thyristors with programmable phase control |
| Voltage measurement | digital AC voltmeter up to 600 VAC |
| Ammeter accuracy | 0.8% of reading plus 0.3% of range |
| Current hold | within 1% of Hold Amps |
| Modes | Normal, Jog-to-Hold, Jog-to-Trip, Current Hold, Memory |
| Measuring circuit | by current or by contacts |
| Control software | WIN HC |
| Calibration | NIST; ISO17025 on request |
Part numbers
Show all part numbers (6)
HC-12C, HC-75C, HC-20C, HC-40C, HCSS1, HCSS2
Request a price and lead time
HC-12C to HC-75C High Current Test Sets, 12000-75000 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the sets test high voltage breakers?
Yes. In a series configuration they provide primary injection testing of high voltage breakers and protective relays during substation maintenance.
What is the current measurement accuracy?
The ammeter is accurate to 0.8% of reading plus 0.3% of range. In Current Hold mode the current is held within 1% of the set Hold Amps.
Is there an automatic test mode?
Jog-to-Hold and Jog-to-Trip run automatically, and the WIN HC program stores each test in a database and produces reports.