HC-1 to HC-5 High Current Test Sets, 1000-5000 A
The HC-1, HC-2, HC-3 and HC-5 portable sets supply output currents from 1000 to 5000 A for testing circuit breakers, relays and current transformers. A timer stops at the moment the device trips, and a memory ammeter holds the peak reading.
- Maximum output current HC-1
- 1000 A
- Maximum output current HC-2
- 2000 A
- Maximum output current HC-3
- 3000 A
- Maximum output current HC-5
- 5000 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The HC range comprises four portable high current sources for testing protective equipment. The HC-1 delivers up to 1000 A, the HC-2 up to 2000 A, the HC-3 up to 3000 A and the HC-5 up to 5000 A. Together they cover circuit breakers, relays and current transformers that need a heavy test current.
Moulded-case breakers can be checked, along with motor overload relays of thermal, magnetic or solid-state design and ground fault trip devices. Current transformers are also within reach, so one set can serve several parts of a switchgear check.
Supply voltage depends on the model. The HC-1 and HC-2 run on 120 VAC or 230 VAC, while the HC-3 and HC-5 require 230 VAC. Mains frequency of 50 Hz or 60 Hz is specified when ordering. Each model has two output ranges: the HC-1, for example, gives 0-120 VAC at 5 A or 0-24 VAC at 25 A.
For timing, the measuring leads are connected to the auxiliary contacts of the device under test or to an open pole. When the contact changes state, the current is switched off and the timer stops. The ammeter with memory keeps the peak value on display so that it can be read after the trip.
Calibration to ISO17025 is available on request.
Technical specifications
| Maximum output current HC-1 | 1000 A |
|---|---|
| Maximum output current HC-2 | 2000 A |
| Maximum output current HC-3 | 3000 A |
| Maximum output current HC-5 | 5000 A |
| Supply HC-1 | 120 VAC, 20 Amp or 230 VAC, 10 Amp |
| Supply HC-2 | 120 VAC, 20 Amp or 230 VAC, 12 Amp |
| Supply HC-3 | 230 VAC, 25 Amp |
| Supply HC-5 | 230 VAC, 50 Amp |
| Mains frequency | 50 Hz or 60 Hz (specified when ordering) |
| Output ranges HC-1 | 0-120 VAC, 5 A; 0-24 VAC, 25 A |
| Output ranges HC-2 | 0-70 VAC, 25 A; 0-14 VAC, 125 A |
| Output ranges HC-3 | 0-15 VAC, 0-200 A; 0-7.5 VAC, 0-400 A |
| Output ranges HC-5 | 0-15 VAC, 0-333 A; 0-10 VAC, 0-500 A |
| Calibration | ISO17025 on request |
Part numbers
Show all part numbers (4)
HC-1, HC-2, HC-3, HC-5
Request a price and lead time
HC-1 to HC-5 High Current Test Sets, 1000-5000 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which devices can the HC sets test?
Moulded-case breakers, thermal, magnetic or solid-state motor overload relays, ground fault trip devices and current transformers. They also serve other applications that need a high current source.
How does the set detect the trip point?
The measuring leads go to the auxiliary contacts or an open pole. When the contact changes state, the current is cut off, the timer stops and the memory ammeter holds the peak value.
What supply voltage is needed?
The HC-1 and HC-2 work from 120 VAC or 230 VAC, and the HC-3 and HC-5 from 230 VAC. Specify 50 Hz or 60 Hz when ordering.
Similar equipment from other manufacturers