FMC flexible magnetic coupler for partial discharge measurement on MV and HV cables, 500 kHz to 50 MHz
The FMC (Flexible Magnetic Coupler) is a flexible partial discharge sensor that couples magnetically to the cable conductor and screen. It is fitted directly on the cable close to a joint or termination, and it works on medium and high voltage cables as well as on GIS and GIL.
- Frequency band
- 500 kHz – 50 MHz
- Operating principle
- inductive coupling
- Dimensions, HV version
- about 500 mm by 120 mm by 10 mm
- Dimensions, MV version
- about 500 mm by 40 mm by 10 mm
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The FMC is used to measure partial discharge on medium and high voltage cables, cable joints, terminations and in GIS and GIL installations. It picks up the magnetic signal produced by partial discharge activity and gives its best results on medium voltage cables. Engineers choose it when other sensors are awkward to fit, or when the equipment cannot be taken out of service. Many sites have no earthing conductors on which HFCT current transformers can be mounted, and the FMC makes measurement possible there.
The sensor works by inductive coupling across a 500 kHz to 50 MHz band. One face is turned towards the object under test, while the other, shielded side rejects external interference. The output is a BNC connector. No power is needed unless optional devices, such as the AFMC amplifier, are used.
Two versions are made, sized to the cable. The high voltage version is about 500 mm long, 120 mm wide and 10 mm high, and suits cables above 100 kV. The medium voltage version is about 500 mm by 40 mm by 10 mm, and is chosen for MV cables of smaller cross section. With the IP68 cover fitted, the overall size is about 710 mm by 170 mm by 100 mm.
The sensor is laid along the cable and bent to follow its shape, then secured with cable ties or tape. Tape suits a single measurement, while ties suit longer installations. It operates from -20°C to +65°C, resists ultraviolet light and oil excellently, and resists acids well.
Technical specifications
| Frequency band | 500 kHz – 50 MHz |
|---|---|
| Operating principle | inductive coupling |
| Dimensions, HV version | about 500 mm by 120 mm by 10 mm |
| Dimensions, MV version | about 500 mm by 40 mm by 10 mm |
| Dimensions with IP68 cover | about 710 mm by 170 mm by 100 mm |
| Connector | BNC |
| Power supply | only for the optional AFMC amplifier |
| Installation | on the cable near a joint or termination |
| Operating temperature | -20°C to +65°C |
| UV and oil resistance | excellent |
| Acid resistance | good |
Request a price and lead time
FMC flexible magnetic coupler for partial discharge measurement on MV and HV cables, 500 kHz to 50 MHz. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which FMC version should I choose?
For cables above 100 kV use the high voltage version, about 500 mm by 120 mm by 10 mm. For MV cables of smaller cross section use the version about 500 mm by 40 mm by 10 mm.
Does the sensor need a power supply?
No. Power is only needed for optional devices, such as the AFMC amplifier.
Can the FMC stay on the cable for long term monitoring?
Yes. For long installations it is secured with cable ties, an IP68 cover is available, and the operating range is -20°C to +65°C.