Falcon 4 four-channel partial discharge monitor for medium voltage equipment
Falcon 4 is an instrument for online partial discharge monitoring in switchgear, cables, transformers and motors at medium voltage. It has four partial discharge channels, one synchronisation channel and an integrated web application.
- Target assets
- MV switchgear, cables, transformers, motors
- Partial discharge channels
- 4
- Amplitude range
- 0.001 to 10 Vp
- Frequency band
- 0.02 to 30 MHz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Falcon 4 is used on medium voltage distribution networks to support maintenance based on equipment condition. Online partial discharge monitoring shows the state of insulation, picks up defects at an early stage, and helps reduce unplanned outages and failures. The instrument receives, analyses and stores partial discharge signals from sensors on switchgear, cables, transformers and motors.
A high frequency current transformer clamp (HFCT) is connected to the instrument. It is fitted without taking the equipment out of service, and a TEV antenna is added as well. A typical arrangement for a medium voltage cubicle places the HFCT on the incoming three core cable and the TEV antenna on the metal enclosure, which covers the terminations in the cable compartment. Installation is non-intrusive, and set-up, clustering and alarms run automatically, so no special qualification is needed.
The instrument has four partial discharge channels, with an amplitude range of 0.001 to 10 Vp, a frequency bandwidth of 0.02 to 30 MHz, 16 bit resolution and a sampling rate of 125 MSa/s. The input impedance is 50 Ω. A 5 MHz high pass filter and sensor power of 9Vdc at 0.2A can be switched on when needed. Signal processing uses the patented T-F Map filtering, which separates discharge pulses from noise.
The synchronisation channel takes 1 to 30 Vrms in the 5 to 500 Hz range, sampled at 1 MSa/s, with a minimum input impedance of 1M Ω. Communication runs through an RJ45 port using OPC-UA and IEC 61850 Ed. 1. Dry contacts with NC/NO configuration, rated 24Vdc at 1A, pass alarms to the control system. The supply is 12 to 24 Vdc with a maximum current of 2 A, and settings and data are viewed in the integrated web application.
Technical specifications
| Target assets | MV switchgear, cables, transformers, motors |
|---|---|
| Partial discharge channels | 4 |
| Amplitude range | 0.001 to 10 Vp |
| Frequency band | 0.02 to 30 MHz |
| Resolution | 16 bit |
| Sampling rate | 125 MSa/s |
| Input impedance | 50 Ω |
| High pass filter | 5 MHz, switchable |
| Sensor power over cable | 9Vdc, 0.2A, switchable |
| Synchronisation channel | 1; 1 to 30 Vrms; 5 to 500 Hz; 1 MSa/s; from 1M Ω |
| Port | RJ45 |
| Protocols | OPC-UA, IEC 61850 Ed. 1 |
| Supply voltage | 12 to 24 Vdc, up to 2 A |
| Dry contacts | NC/NO, 24Vdc, 1A |
| Interface | integrated web application |
Request a price and lead time
Falcon 4 four-channel partial discharge monitor for medium voltage equipment. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many partial discharge channels does Falcon 4 have?
Four partial discharge channels, with 16 bit resolution and a sampling rate of 125 MSa/s, plus one synchronisation channel.
Does the equipment need to be taken out of service to fit the sensors?
No. The HFCT clamp is fitted without taking the equipment out of service, and the TEV antenna is fixed to the metal enclosure.
How does the instrument send data and alarms?
Data goes over the RJ45 port using OPC-UA and IEC 61850 Ed. 1, and alarms are also given by dry contacts rated 24Vdc, 1A.