International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

F8300 chassis for up to seven F8 modules, protection relay testing

The F8300 is an F8 series chassis for up to seven interchangeable modules, used for three-phase testing of conventional, digital and hybrid protection schemes. Having more modules than the four-module F8200 allows checks of differential and distance protection, and of generator and transformer protection.

Number of modules
up to seven F8 modules
Voltage module (per channel)
150 V @ 150 VA
Voltage module (paralleled)
300 V @ 300 VA
Current module (per channel)
25 A @ 150 VA

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The F8300 is used as a universal tool for testing protection in power generation, transmission and distribution. Typical tasks include differential and distance protection, generator protection schemes, differential protection of transformers and lines, three-phase and phase-to-phase tests of transformer protection, testing of reclosers, transducers and Class 2 meters, and end-to-end tests.

The chassis holds up to seven F8 modules in any arrangement, and the modules are exchanged without complicated operations. Fitting other F8 modules adapts the set to new types of test. The HVA voltage module works as a 150 V source at 150 VA per channel, or as a 300 V source at 300 VA in parallel mode. The HVA current module has channels of 25 A at 150 VA; in parallel it gives 50 A continuously at 300 VA, 90 A at 300 VA for 30 seconds in transient mode, and a 50 A DC output.

The battery simulator delivers 6 to 300 V at 90 W. The HD Logic I/O module has eight pairs of inputs and outputs, with two sockets on each port, for connecting relay contacts. Internal time synchronisation supports GPS, IRIG-B, PTP, USB and Ethernet over copper or optical links, and GPS synchronisation uses the F8895 satellite antenna.

The set conforms to IEC 61850 and is compatible with the test procedures of Protection Suite v5 and RTS v7, so existing test programmes carry over without rework. Programmable coloured LED rings show the state of sources and contacts. The portable version has protective bumpers on the corners and edges and carrying accessories, while laboratories can mount it in 19-inch racks. The smaller F8200 model is designed for four modules.

Technical specifications

Number of modulesup to seven F8 modules
Voltage module (per channel)150 V @ 150 VA
Voltage module (paralleled)300 V @ 300 VA
Current module (per channel)25 A @ 150 VA
Current module (paralleled, continuous)50 A @ 300 VA
Transient current90 A @ 300 VA for 30 seconds
DC current output50 A
Battery simulator6 to 300 V, 90 W
HD Logic I/O moduleeight pairs of inputs and outputs, two sockets each
Time synchronisationGPS, IRIG-B, PTP, USB, Ethernet (copper or optical)
ComplianceIEC 61850
Configurationportable with bumpers, or 19-inch rack

Part numbers

Show all part numbers (1)

F8300

Request a price and lead time

F8300 chassis for up to seven F8 modules, protection relay testing. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How does the F8300 differ from the F8200?

The F8300 holds up to seven F8 modules and the F8200 up to four, so the F8300 suits three-phase testing of transformer and generator differential protection.

What is the transient current output of the HVA current module?

It gives 90 A at 300 VA for 30 seconds in transient mode, while continuous output in parallel is 50 A at 300 VA.

Can the F8300 be mounted in a rack?

Yes, there is a 19-inch rack mounting option, and for field work the portable version comes with bumpers and carrying accessories.