F6150sv power system simulator for IEC 61850 protection testing, 210 A with F6005

The F6150sv is a power system simulator in the F6 series for testing protection devices and schemes based on IEC 61850. It works with the process bus and station bus through sampled values and GOOSE messages, and delivers up to 210 A with the F6005 amplifier.

Voltage sources
6
High-level analogue sources
up to 12
Low-level analogue sources
up to 12
Current limit, with F6005 amplifier
210 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The F6150sv is used for testing digital substation protection, where devices exchange data under IEC 61850. It tests systems at the process bus and station bus levels using sampled values and GOOSE messages, and sampled values require the F6870 option. The unit simulates three IEC 61850 9-2LE sampled-value streams through an optical port and an RJ45 copper port, publishes GOOSE messages and subscribes to them from several IEDs.

Beyond the digital interfaces, the F6150sv carries out conventional tests: calibration and checking of microprocessor relays and relays with a high burden, simulation of power system states and transients, checking of class 0.2 current transformers and converters, and end-to-end tests of protection schemes with communication channels, time-synchronised by GPS. Up to 12 high-level analogue sources, six voltage and six current, can be configured for bench tests of complex protection schemes.

Voltage sources work in the configurations 6 x 150 V @ 75 VA, 3 x 300 V @ 150 VA and 1 x 600 V @ 300 VA, and on DC at 3 x 424 V @ 150 W. Full power is delivered into resistive, inductive and capacitive loads at currents of 6 x 35 A, 3 x 70 A or 1 x 210 A. The AC amplitude error is typically below 0.02 % and guaranteed below 0.09 %, THD is typically below 0.02 % and guaranteed below 0.1 %, and the frequency bandwidth runs from DC to 3 kHz at full power.

Three versions are offered. The F6150sv (Premier) has 12 high-level analogue sources and six AC/DC amplifiers, with AC currents of 1x180 A, 3x60 A and 6x30 A. The F6150sv-SGD for distribution grids has eight high-level sources and four amplifiers, with 1x120 A, 2x60 A and 4x30 A. The F6150sv-IEC works with 12 low-level analogue sources and, with the F6005 amplifier, gives 1x210 A, 3x70 A and 6x35 A.

The unit has 8 logic inputs, 4 logic outputs and a battery simulator of 6 to 300 V DC. It runs on 105–264 V, 47–63 Hz and draws up to 2600 W. It weighs 19.05 kg and measures 38 x 24 x 45.7 cm in a Type 1 / IP20 enclosure, with Wi-Fi built in. It meets EN 61010-1, UL 61010-1 and CSA 27.2 # 61010-1 safety requirements, the IEC 61000-6-2:2005 immunity standard and ANSI/IEEE c37.90. Production is certified to ISO 9001, ISO/IEC 17025 and ISO/IEC 17034.

Technical specifications

Voltage sources6
High-level analogue sourcesup to 12
Low-level analogue sourcesup to 12
Current limit, with F6005 amplifier210 A
Logic inputs8
Logic outputs4
AC amplitude error<0.02 % typical, <0.09 % guaranteed
THD<0.02 % typical, <0.1 % guaranteed
Frequency bandwidthDC – 3 kHz at full power
Battery simulator6 – 300 V DC
Supply105–264 V, 47–63 Hz
Maximum power consumption2600 W
Weight19.05 kg
Dimensions38 x 24 x 45.7 cm
Enclosure classType 1 / IP20

Part numbers

Show all part numbers (2)

F6150sv, F6150sv-SGD and F6150sv-IEC

Request a price and lead time

F6150sv power system simulator for IEC 61850 protection testing, 210 A with F6005. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What is needed to work with IEC 61850 sampled values?

The F6870 option is needed, after which the unit simulates three IEC 61850 9-2LE sampled-value streams through an optical port and an RJ45 copper port.

How does the F6150sv-SGD differ from the base F6150sv?

The F6150sv-SGD has 8 high-level sources and 4 amplifiers with 1x120 A, 2x60 A and 4x30 A, while the base F6150sv has 12 sources and 6 amplifiers.

How accurate is the signal generation?

Amplitude error is typically below 0.02 % and guaranteed below 0.09 %, THD is typically below 0.02 %, and the bandwidth runs from DC to 3 kHz.