International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

EZCT-2KA 2 kV current transformer tester with 1000-record memory

Portable, microprocessor-based third-generation current transformer tester. It runs the magnetisation characteristic test automatically, checks the transformation ratio and polarity, and measures winding resistance without re-cabling the leads.

Type
portable CT tester
Method
C57.13.1 and C57.12.90 (ANSI/IEEE)
Output voltage
0–50 Vac @ 10A, 0–300 Vac @ 8A, 0–500 Vac @ 5A, 0–1200 Vac @ 2A, 0–2000 Vac @ 1.2A
Voltage measurement
0–2200 Vac, ±1.0 % of reading, ±1 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The EZCT-2KA is designed to test current transformers at substations during commissioning and routine maintenance. It performs excitation (saturation) testing, checks the transformation ratio and polarity, and measures winding resistance and phase angle. The measurements follow the ANSI/IEEE methods.

All measuring leads are connected once to the transformer's X1 to X5 terminals, so no re-cabling is needed during the test. The test voltage rises and falls automatically without operator involvement. An excitation voltage of up to 2000 Vac allows high-power current transformers to be tested.

Excitation output ranges are 0–50 Vac at 10 A, 0–300 Vac at 8 A, 0–500 Vac at 5 A, 0–1200 Vac at 2 A and 0–2000 Vac at 1.2 A. Voltage is measured over 0–2200 Vac with ±1.0 % of reading ±1 V accuracy, and current over 0–10 A with ±1.0 % ±0.02 A. The transformation ratio spans 0.8 to 10000 with errors from ±0.1 % to ±1.5 % depending on range, and the phase angle covers 0–360° at ±1.0°. Winding resistance is read from 100 µΩ to 20 Ω at 1 µΩ resolution, with 2 % of reading ±10 µΩ accuracy below 1.99 Ω and 1.5 % ±2 mΩ from 2 to 20 Ω.

The memory stores 1000 test records, each holding up to ten sets of excitation, resistance and ratio data, along with 128 test plans of ten voltage and current settings each. Record headers hold the company, substation, bay, CT serial number, operator and comments. The unit plots several saturation curves, prints a report on its built-in 4.5-inch thermal printer and shows results on a backlit 240 x 128 pixel LCD. It has USB and Bluetooth connections and a USB flash drive port, and Windows-based CT analysis software is included.

It runs on 100–120 V AC or 200–240 V AC, set at the factory, at 50/60 Hz, and measures 42.7 x 32.0 x 26.9 cm with a weight of 21 kg. The operating temperature is -10 to +50 °C, storage -30 to +70 °C, with humidity up to 90 % RH at 40 °C without condensation and altitude up to 2000 m. The supplied cables are a 20-foot X cable set, a 35-foot H cable set, a power cord, a USB cable and a carrying bag, while a shipping case is available as an option.

Technical specifications

Typeportable CT tester
MethodC57.13.1 and C57.12.90 (ANSI/IEEE)
Output voltage0–50 Vac @ 10A, 0–300 Vac @ 8A, 0–500 Vac @ 5A, 0–1200 Vac @ 2A, 0–2000 Vac @ 1.2A
Voltage measurement0–2200 Vac, ±1.0 % of reading, ±1 V
Current measurement0–10 A, ±1.0 % of reading, ±0.02A
Transformation ratio0.8–999 ±0.1 %; 1000–1999 ±0.3 %; 2000–4999 ±1 %; 5000–10000 ±1.5 %
Phase angle0–360°, ±1.0°
Winding resistance100 µΩ – 20 Ω, 1 µΩ resolution
Resistance accuracy100 µΩ – 1.99 Ω: 2 % ±10 µΩ; 2 Ω – 20 Ω: 1.5 % ±2 mΩ
Displaybacklit LCD 240 x 128 pixels
Printerbuilt-in 4.5-inch thermal printer
InterfacesUSB, Bluetooth, USB flash drive port
Memory1000 records, 128 test plans
Power100–120 V AC or 200–240 V AC, 50/60 Hz
Dimensions42.7 x 32.0 x 26.9 cm
Weight21 kg
Operating temperature-10 °C … +50 °C
SafetyUL 61010A-1 and C22.2 No. 1010.1-92 (CAN/CSA)

Part numbers

Show all part numbers (2)

9118-UC, 9119-UC and 9118-SC

Request a price and lead time

EZCT-2KA 2 kV current transformer tester with 1000-record memory. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How does the EZCT-2KA differ from the EZCT-2000C?

It has no insulation resistance or burden test functions, but it stores 1000 records, weighs 21 kg, and measures winding resistance up to 20 Ω at 1 µΩ resolution.

Which part numbers are available?

9118-UC is for a 110 V supply, 9119-UC for 220 V, and 9118-SC is the transport case.

Can all CT terminals be connected at once?

Yes, the leads are connected to terminals X1 to X5 and the test runs without re-cabling.