EZCT-2000C 2 kV current transformer tester with insulation and burden measurement

Portable, microprocessor-based third-generation current transformer tester. It records the magnetisation characteristic, checks the transformation ratio, polarity and phase angle, and measures winding resistance, insulation resistance and secondary burden.

Type
portable CT tester
Method
C57.13.1 and C57.12.90 (ANSI/IEEE)
Excitation voltage
0–50 Vac @ 10A, 0–300 Vac @ 10A, 0–500 Vac @ 5A, 0–1200 Vac @ 1.2A, 0–2000 Vac @ 1A
Current source
1–20A @ 0–15 Vac

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The EZCT-2000C is used to test current transformers during commissioning and at scheduled inspections. It carries out saturation (magnetisation) tests, checks the transformation ratio, polarity and phase angle, and measures insulation resistance, winding resistance and the burden of the secondary circuit. The measurements follow the ANSI/IEEE methods, and the knee point is determined as well.

The test leads are connected once to all current transformer terminals, and the full test then runs automatically without re-cabling or operator involvement. The tester works stand-alone or is controlled from a PC over USB or Bluetooth, and Windows-based analysis software is supplied.

Excitation voltage ranges are 0–50 Vac at 10 A, 0–300 Vac at 10 A, 0–500 Vac at 5 A, 0–1200 Vac at 1.2 A and 0–2000 Vac at 1 A. A built-in current source of 1–20 A at 0–15 Vac covers burden checks. Voltage is read over 0–2200 Vac with ±1.0 % of reading ±1 V accuracy, and current over 0–10 A with ±1.0 % ±0.02 A. The transformation ratio is measured from 0.8 to 10000 with errors from ±0.1 % to ±1.5 % depending on range, and phase angle over 0–360° with ±1.0° accuracy. Winding resistance runs from 100 µΩ to 30 Ω, and insulation resistance from 2 to 500 MΩ at 500 or 1000 V DC.

The memory holds 140 test records, each with up to ten sets of magnetisation, resistance and ratio data, plus 128 test plans. Record headers capture the company, substation, bay, CT serial number, operator and comments. The unit plots several saturation curves on one graph, prints results on a built-in 4.5-inch thermal printer and shows them on a backlit 240 x 128 pixel LCD that stays readable in bright sunlight. Data can also be saved to a USB flash drive.

It runs on 100–120 V AC or 200–240 V AC, set at the factory, at 50/60 Hz, and measures 48.3 x 33 x 40.1 cm with a weight of 33.1 kg. The operating range is -10 to +50 °C, storage -30 to +70 °C, with humidity up to 90 % RH at 40 °C without condensation and altitude up to 2000 m. The X terminals are rated for a working voltage of 2200 Vac. The package includes a set of 20-foot X cables, a 35-foot H cable, current source and insulation test cables and a transport case.

Technical specifications

Typeportable CT tester
MethodC57.13.1 and C57.12.90 (ANSI/IEEE)
Excitation voltage0–50 Vac @ 10A, 0–300 Vac @ 10A, 0–500 Vac @ 5A, 0–1200 Vac @ 1.2A, 0–2000 Vac @ 1A
Current source1–20A @ 0–15 Vac
Voltage measurement0–2200 Vac, ±1.0 % of reading, ±1 V
Current measurement0–10A, ±1.0 % of reading, ±0.02A
Transformation ratio0.8–999 ±0.1 %; 1000–1999 ±0.3 %; 2000–4999 ±1 %; 5000–10000 ±1.5 %
Phase angle0–360°, ±1.0°
Winding resistance100 µΩ – 30 Ω, 2 % of reading, ±1 count, ±10 µΩ
Insulation resistance2–500 MΩ, 3 % of reading, 500–1000 Vdc
Displaybacklit LCD 240 x 128 pixels, 114 x 64 mm
Printerbuilt-in 4.5-inch thermal printer
InterfacesUSB, Bluetooth, USB flash drive port
Memory140 records, 128 test plans
Power100–120 V AC or 200–240 V AC, 50/60 Hz
Dimensions48.3 x 33 x 40.1 cm
Weight33.1 kg
Operating temperature-10 °C … +50 °C
SafetyUL 61010A-1 and C22.2 No. 1010.1-92 (CAN/CSA)

Part numbers

Show all part numbers (2)

9101-UC, 9102-UC and 9101-SC

Request a price and lead time

EZCT-2000C 2 kV current transformer tester with insulation and burden measurement. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How do the part numbers 9101-UC and 9102-UC differ?

9101-UC is for a 110 V supply, 9102-UC for 220 V, and 9101-SC is the transport case.

Do the test leads have to be moved during a test?

No. The leads are connected to all current transformer terminals once, and the full test cycle runs automatically.

What is the highest excitation voltage the tester supplies?

Up to 2000 Vac at 1 A, and the X terminals are rated for a working voltage of 2200 Vac.