International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

EKAM primary current injection system, up to 5000 A at 15–500 Hz

A fully automatic primary injection test system built from two portable units: a control unit with a large graphical display and a BUX current unit. It checks current transformers, circuit breakers, earthing resistance, step and touch voltages and line impedance.

Output current
up to 2000, 3000 or 5000 A (BUX 2000, BUX 3000, BUX 5000)
AC output voltage
(0÷220) V AC
Frequency
15÷500 Hz, resolution 10 mHz
Phase angle
(0÷360) °, resolution 0.01 °

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The eKAM is used to test substation equipment with a high primary current. The system checks the transformation ratio, polarity and secondary burden of current transformers, including those with a digital IEC 61850-9-2 output, and it measures circuit breaker operating times and the impedance of earthing and lines. With the STLG option it also measures step and touch voltages and the resistance of the earthing system. A shortened time-characteristic test is provided as well.

The kit consists of two portable units. The control unit, with a colour TFT display of 640 x 480 pixels and a working area of 132 x 99 mm, sets the output parameters and measures and stores the results. The BUX current unit delivers the high current: BUX 2000 reaches 2000 A, BUX 3000 reaches 3000 A and BUX 5000 reaches 5000 A, and special settings allow 7000 A on the BUX 5000. BUX 2000 gives 2.6 V in two turns, BUX 3000 gives 1.6 V in one turn and BUX 5000 gives 1.3 V in one turn. Without cables and clamps they weigh 18 kg, 15 kg and 19 kg respectively.

The control unit produces a variable AC output of 0 to 220 V at 15 to 500 Hz, with a frequency resolution of 10 mHz. Measuring inputs cover AC and DC current up to 10 A, AC voltage up to 300 V and 3 V, and DC voltage up to 10 V, with guaranteed errors of ±0.05 % to ±0.10 % of reading. Phase angle is measured from 0 to 360° with 0.01° resolution, and the timer has 1 ms resolution over a range of 9.999 s. Memory holds up to 64 test plans and more than 1000 test results. The unit connects to a PC over USB and Ethernet, and control and data analysis are handled in the TDMS software.

Options include an STLG transformer with five taps at 11, 22, 35, 55 and 105 A AC, delivering 1.800 VA continuously, a power factor correction module for the STLG, an STSG earthing module rated at 25 kA for 100 ms, a ground grid test kit, clamp meters up to 400 A AC and a stainless steel folding trolley.

The system runs on 100 to 230 V ±15 %, 48 to 62 Hz, with a supply current of up to 16 A and normal consumption below 1 kW. The control unit weighs 17 kg and measures 450 x 400 x 230 mm. It works from -10 to 55 °C, can be stored from -20 to 70 °C, tolerates 5–95 % relative humidity without condensation and carries an IP 2X rating.

Technical specifications

Output currentup to 2000, 3000 or 5000 A (BUX 2000, BUX 3000, BUX 5000)
AC output voltage(0÷220) V AC
Frequency15÷500 Hz, resolution 10 mHz
Phase angle(0÷360) °, resolution 0.01 °
AC current input error (up to 10 A)±0.10 % of reading
DC voltage input error (up to 10 V)±0.05 % of reading
Timer1 ms resolution, up to 9.999 s
Memoryup to 64 test plans, over 1000 results
Displaycolour TFT 640 x 480, 132 x 99 mm
InterfacesUSB, Ethernet, IEC 61850-9-2
Power supply100÷230 V ±15 %, 48÷62 Hz, up to 16 A
Control unit weight17 kg
Control unit dimensions450 x 400 x 230 mm
BUX 2000 / 3000 / 5000 weight18 / 15 / 19 kg
Clamps5 to 60 mm opening, 41 kA ÷ 1 s, EN 61230
Operating temperature-10 … 55 °C
Relative humidity5-95 % without condensation
Protection degreeIP 2X

Part numbers

Show all part numbers (14)

49175, 56175, 50175, 63175, PII70175, PII71175, PII76175, PII72175, PII73175, PII74175, PII18175, PII85175, PII77175, PII79175

Request a price and lead time

EKAM primary current injection system, up to 5000 A at 15–500 Hz. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What is the maximum current the system can output?

Up to 2000, 3000 or 5000 A depending on the BUX unit, and the BUX 5000 can reach 7000 A with special settings.

Can step and touch voltages be measured?

Yes, with the STLG option the system measures step and touch voltages and the resistance of the earthing system, using STLG current from 11 to 105 A AC.

Can digital current transformers be tested?

Yes, the system supports the IEC 61850-9-2 protocol for testing transformers that send sampled values.

Similar equipment from other manufacturers