DRTS 66 relay protection test kit with 6 current and 6 voltage outputs
The DRTS 66 is the top model of the series, with six current generators, six voltage generators and a battery simulator. It supplies full three-phase current and voltage systems from both sides of the equipment, which suits differential protection, synchronising relays and multi-phase relays.
- Generators
- 6 current, 6 voltage and battery simulator
- Current outputs
- six of 0–32 A, three of 0–64 A, one of 0–128 A
- Current output power
- six at 430 VA (32 A), three at 860 VA (64 A), one at 1000 VA (64 A)
- Voltage outputs
- six of 0–300 V at 100 VA, one of 0–600 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The six voltage generators, each giving 0 to 300 V at 100 VA, can supply two independent three-phase systems. This suits relays that compare two voltage sources, such as synchronising checks or automatic transfer switching. Connected in series, the outputs give a single 0 to 600 V channel.
Six current outputs of 0 to 32 A can be paralleled into three 0 to 64 A channels or one 0 to 128 A channel. Each channel delivers 430 VA at 32 A, the three-channel arrangement gives 860 VA per channel at 64 A, and the single-output arrangement gives 1000 VA at 64 A. Voltage and current accuracy is better than 0.05%.
Communication runs over USB and Ethernet, with an IEC 61850 interface and IRIG-B time synchronisation. The set supports GOOSE under IEC 61850-8 and sampled values under IEC 61850-9-2. Tests are built and run in TDMS 7 or TDMS Pro, which contains a library of relays from the major manufacturers.
The front panel carries a 5.7 inch colour display with 320 x 240 pixels for manual control, and an optional industrial touch screen tablet provides local touch control. The battery simulator supplies 0 to 260 V DC at 1 A and 50 W, so relays can be kept powered during tests.
Accessories include the HPB 400 and HPB 600 current amplifiers, the AMI 332 and AMI 632 modules and the PLCK polarity indicator. Carrying options are a rigid plastic case, a rigid case or a soft bag. The set runs from a single-phase 85 to 264 V AC supply at 45 to 65 Hz, and its enclosure measures 150 x 466 x 423 mm. The operating range is 0 to 55 °C, storage is -25 to 70 °C, humidity is 5 to 95% without condensation, and altitude is up to 2000 m. It conforms to EN 61326:2006 and CEI EN 61010-1.
Technical specifications
| Generators | 6 current, 6 voltage and battery simulator |
|---|---|
| Current outputs | six of 0–32 A, three of 0–64 A, one of 0–128 A |
| Current output power | six at 430 VA (32 A), three at 860 VA (64 A), one at 1000 VA (64 A) |
| Voltage outputs | six of 0–300 V at 100 VA, one of 0–600 V |
| Accuracy | better than 0.05% |
| Battery simulator | up to 260 V DC at 1 A and 50 W |
| Interfaces | IEC 61850, USB, Ethernet, IRIG-B |
| Display | 5.7 inch, 320 x 240 pixels |
| Mains supply | 85–264 V AC, single phase, 45–65 Hz |
| Dimensions | 150 x 466 x 423 mm |
| Operating temperature | 0–55 °C |
| Storage temperature | -25 to 70 °C |
| Relative humidity | 5–95%, without condensation |
| Altitude | up to 2000 m |
Part numbers
Show all part numbers (2)
45170, 40170
Request a price and lead time
DRTS 66 relay protection test kit with 6 current and 6 voltage outputs. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
When are all six voltage generators needed?
When a relay compares two three-phase voltage systems, for example in synchronism checks or automatic transfer switching. The DRTS 66 supplies 6 x 0…300 V at 100 VA at the same time.
Does the set support IEC 61850-9-2?
Yes. Alongside GOOSE under IEC 61850-8, it supports sampled values under IEC 61850-9-2 and can synchronise to IRIG-B.
What is the difference between codes 45170 and 40170?
Code 45170 is the basic 6I/6V module. Code 40170 adds IRIG-B synchronisation and an output expansion module.