International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

DRTS 34 Relay Test Set with Four Voltage and Three Current Generators

The DRTS 34 is an automatic test set with three current generators, four voltage generators and a battery simulator. It checks protection relays, transducers, energy meters and power quality meters during commissioning and substation maintenance.

Generators
3 current, 4 voltage and a battery simulator
Current outputs
3 x 0 to 32 A, 1 x 0 to 96 A
Current output power
430 VA per output at 32 A, and 1000 VA on the single output at 64 A
Voltage output channels
4 x 0 to 300 V and 1 x 0 to 600 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

A fourth voltage generator is useful where zero sequence or synchronising voltage has to be applied separately from the three phase voltages. The unit covers line and distribution network protection, low power units, DC relays and smart grid protection, as well as single and three phase relay tests, energy meters, transducers and power quality meters.

Current outputs are 3 x 0 to 32 A, or 1 x 0 to 96 A with the outputs paralleled. Current output power is 430 VA on each of the three outputs at 32 A, and 1000 VA on the single output at 64 A. Voltage outputs run from 0 to 300 V on each of the four channels, and can be combined in series for 0 to 600 V on one output. Typical current accuracy is ±0.02% of reading and ±0.01% of range, guaranteed at 0.04% of reading and ±0.01% of range, while voltage accuracy is guaranteed at 0.06% of reading and ±0.015% of range. Distortion is typically 0.015%, guaranteed 0.03%, and current resolution is 0.1 mA at 32 A.

Current output frequency runs from 0 to 3000 Hz. For voltage, the upper frequency is 3 kHz at 60 V, 2 kHz at 125 V and 700 Hz at 300 V. Transients can be reproduced up to 5000 Hz. Frequency error is 0.5 ppm, and the angle can be set from -360° to +360° with a resolution of 0.001°. An auxiliary DC output of 0 to 260 V, 1 A and 50 W supplies the relay during testing.

There are 12 digital inputs rated from 4.5 to 300 V DC, or 24 to 230 V AC, and with the Transcope option 10 inputs work up to 600 V. Four make and break outputs switch 300 V and 8 A AC at 2400 VA, or 300 V, 8 A and 50 W DC. The unit communicates by USB and Ethernet, offers an IEC 61850 interface, and runs tests in the TDMS software, which includes a relay library. Internal memory is 256 MB.

Power comes from 85-264 V AC, 45-65 Hz. Consumption is under 150 W when idle, and reaches 1600 W at 115 V or 2700 W at 230 V. The aluminium 3U enclosure has IP2x protection, measures 150 x 466 x 423 mm and weighs 18 kg. Operating temperature is 0-55 °C, storage is -25 to 70 °C, and use is allowed up to 2000 m altitude. The base model is code 22170, while the 20170 version adds IRIG-B timing and an expansion module for outputs.

Technical specifications

Generators3 current, 4 voltage and a battery simulator
Current outputs3 x 0 to 32 A, 1 x 0 to 96 A
Current output power430 VA per output at 32 A, and 1000 VA on the single output at 64 A
Voltage output channels4 x 0 to 300 V and 1 x 0 to 600 V
Current accuracytypical ±0.02% of reading and ±0.01% of range; guaranteed 0.04% of reading and ±0.01% of range
Distortiontypical 0.015%, guaranteed 0.03%
Current output frequency0-3000 Hz
Angle resolution0.001°
Auxiliary DC output0 to 260 V, 1 A, 50 W
Digital inputs12, from 4.5 to 300 V DC (24-230 V AC)
Digital outputs4; AC 300 V, 8 A, 2400 VA; DC 300 V, 8 A, 50 W
InterfacesIEC 61850, USB, Ethernet
Supply85-264 V AC, 45-65 Hz
Power consumption1600 W at 115 V, 2700 W at 230 V
Dimensions150 x 466 x 423 mm
Weight18 kg
Operating temperature0-55 °C

Part numbers

Show all part numbers (2)

22170, 20170

Request a price and lead time

DRTS 34 Relay Test Set with Four Voltage and Three Current Generators. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What is the fourth voltage generator for?

It provides a separate voltage, such as zero sequence or synchronising voltage, alongside the three phase voltages. All four voltage outputs have a range of 0 to 300 V.

What is the current output accuracy?

Typical accuracy is ±0.02% of reading and ±0.01% of range, guaranteed at 0.04% of reading and ±0.01% of range. Current resolution is 0.1 mA at 32 A.

How do codes 22170 and 20170 differ?

22170 is the base model of the DRTS 34. The 20170 version also has IRIG-B timing and an output expansion module.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides