DoblePRIME iO data recorder for current, voltage, temperature and relay inputs
The doblePRIME iO is a data recorder that takes current, voltage, temperature and relay inputs into the doblePRIME system. It works as a stand-alone monitor with direct sensor inputs or as a module of the platform, with no proprietary software or cloud service needed.
- Input options
- 16 DI; 6 DI and 6 relays; 8 AI; 4 AO; 4 DI, 4 DIO and 4 AI; 6 RTD
- Connection
- screw terminals
- Processor
- ARM11 700 MHz
- Memory
- 512 MB RAM, 4 GB flash
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The doblePRIME iO gathers and displays data from several sensors and sources at a site, including load and other operational parameters, tap position indicators and signals from devices made by other suppliers. It is used in transformer condition monitoring systems alongside monitors for dissolved gases, partial discharge and bushings, and it also works as a stand-alone device with direct sensor connections.
Data are stored in the device and shown through the doblePRIME user interface. Access is local or remote, over an intranet or an external network, in line with the applicable security policies. No proprietary software or cloud connection is needed, and the dashboard can be viewed on a phone, tablet or PC.
The input mix is chosen for each job: 16 DI, 6 DI and 6 relays, 8 AI, 4 AO, 4 DI with 4 DIO and 4 AI, or 6 RTD. Analogue inputs take current, voltage and temperature sensor signals, and the wiring connects to screw terminals.
The computing side has an ARM11 processor at 700 MHz, with 512 MB of RAM, 4 GB of flash and 4 GB of eMMC storage for applications and data. Communication runs through USB 2.0, an isolated RS485 port that supports Modbus RTU master or slave, or DNP3 master or outstation, and 10/100 BaseT Ethernet for DNP3, Modbus TCP, HTTP and WebDAV server. IEC 61850 is available on request. The unit is fully networkable and works with doblePRIME modules and other systems.
The housing is anodised aluminium measuring 200 x 153 x 82 mm and weighing 1.5 kg. It can be panel-mounted, DIN-rail mounted or fitted on rubber feet. Power comes from an external 24 V DC @ 1 A supply. Operating temperature is -20 to +50 °C, storage is -20 to +70 °C, and humidity is 0 to 95% without condensation.
Technical specifications
| Input options | 16 DI; 6 DI and 6 relays; 8 AI; 4 AO; 4 DI, 4 DIO and 4 AI; 6 RTD |
|---|---|
| Connection | screw terminals |
| Processor | ARM11 700 MHz |
| Memory | 512 MB RAM, 4 GB flash |
| Storage | 4 GB eMMC flash |
| USB | USB 2.0 |
| Serial interface | isolated RS485 (Modbus RTU master/slave or DNP3 master/outstation) |
| Ethernet | 10/100 BaseT (DNP3, Modbus TCP, HTTP, WebDAV server) |
| IEC 61850 | available on request |
| Power supply | 24 V DC @ 1 A |
| Operating temperature | -20 °C to +50 °C |
| Storage temperature | -20 °C to +70 °C |
| Humidity | 0–95% without condensation |
| Dimensions (H x W x D) | 200 x 153 x 82 mm |
| Weight | 1.5 kg |
| Housing | anodised aluminium |
| Mounting | panel, DIN rail or rubber feet |
Request a price and lead time
DoblePRIME iO data recorder for current, voltage, temperature and relay inputs. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Is a cloud connection needed?
No. Data are available locally or remotely through an intranet or an external network, without proprietary software or cloud services.
Which input configurations are available?
16 DI; 6 DI and 6 relays; 8 AI; 4 AO; 4 DI, 4 DIO and 4 AI; or 6 RTD.
Which protocols are supported?
Modbus RTU and Modbus TCP, DNP3, HTTP and WebDAV server. IEC 61850 is available on request.