International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

DoblePRIME Analytics gateway and analysis core for transformer monitoring

doblePRIME Analytics is the data hub and analysis unit of the doblePRIME monitoring platform. It collects data from monitors, sensors and operational systems, and produces condition analysis and alarms for a single asset or a whole substation.

Operating system
Linux
Processor
Intel Atom 1.86 GHz
RAM
4 GB
Storage
128 GB SSD

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

doblePRIME Analytics sits at the centre of a substation's equipment monitoring setup. It collects data from monitors, sensors and operational sources, runs the analysis and raises warnings and alarms for each monitor or any combination of them. It can anchor monitoring for one transformer or one substation, or pass that site's data on to a risk management system.

All monitoring components of the platform appear on a single dashboard, including dissolved gas, thermal, partial discharge and bushing monitors. The unit accepts direct signals from analogue sources such as temperature probes and voltage or current measuring devices. A built-in expert system with advanced analytics learns the characteristics of the equipment, produces condition and operating status analyses, and checks the archive and integrity of the data.

The computing side runs Linux on an Intel Atom processor at 1.86 GHz, with 4 GB of RAM and a 128 GB SSD. Communication uses two gigabit LAN ports with galvanic isolation and IEEE 1588 support, one USB 2.0 port, two RS232 ports, two RS485 ports with 2.5 kV isolation, and VGA and HDMI outputs. Supported protocols are Modbus RTU master and slave, Modbus TCP client and server, and DNP3 master and outstation.

Local signals are handled by four digital inputs for dry or wet contacts and four differential analogue inputs for 4 to 20 mA signals at 16-bit resolution. Four LEDs show Status, Info, Warning and Action. The anodised aluminium housing measures 200 x 220 x 66 mm and weighs 2 kg, and it can be panel-mounted, DIN-rail mounted or fitted on rubber feet.

The unit is powered by an external 24 V DC @ 1 A supply. Operating temperature is -20 to +60 °C, or -40 to +75 °C in the extended version. Storage is -20 to +70 °C, and humidity is 0 to 95% without condensation.

Technical specifications

Operating systemLinux
ProcessorIntel Atom 1.86 GHz
RAM4 GB
Storage128 GB SSD
LAN (gigabit)2, isolated, IEEE 1588
RS4852 (2.5 kV isolation)
RS2322
VideoVGA, HDMI
Digital inputs4, dry or wet contact
Analogue inputs4, 4–20 mA, 16-bit, differential
ProtocolsModbus RTU master/slave, Modbus TCP client/server, DNP3 master/outstation
Status LEDs4: Status, Info, Warning, Action
Power supply24 V DC @ 1 A
Operating temperature-20 °C to +60 °C
Extended temperature range-40 °C to +75 °C
Storage temperature-20 °C to +70 °C
Humidity0–95% non-condensing
Dimensions (H x W x D)200 x 220 x 66 mm
Weight2 kg
Housinganodised aluminium

Request a price and lead time

DoblePRIME Analytics gateway and analysis core for transformer monitoring. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which protocols does the unit use to exchange data?

Modbus RTU master and slave, Modbus TCP client and server, and DNP3 master and outstation are supported over the gigabit LAN ports and the RS485 ports.

Can analogue sensors be connected directly?

Yes. There are four differential analogue inputs for 4 to 20 mA signals with 16-bit resolution, and four digital inputs for dry or wet contacts.

What temperature range does the unit tolerate?

Operating temperature is -20 to +60 °C, or -40 to +75 °C in the extended version.