DigiTMR S2 circuit breaker analyser with thermal printer

The DigiTMR S2 is a digital circuit breaker analyser that runs stand-alone or under computer control. It measures contact time, stroke, velocity, over-travel and contact wipe for every breaker operation, and prints the results on its built-in printer.

Type
portable circuit breaker analyser
Dry-contact channels
3, main contact and insertion resistor contact in each
Timing windows
1, 10 or 20 seconds
Timing resolution
±50 microseconds at 1 s, ±500 microseconds at 10 s, ±1.00 ms at 20 s

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The instrument is used in commissioning and periodic checks on circuit breakers, including extra-high-voltage types. It analyses contact motion for every breaker operation: open, close, open–close, close–open and open–close–open. Results appear on a 240 x 128 pixel backlit LCD that can be read in bright sunlight and in low light, and the built-in 4.5-inch thermal printer outputs graphic travel waveforms and tables of test results.

Three dry-contact channels each detect the main contact and the insertion resistor contact. A contact counts as closed below 20 ohms and open above 5,000 ohms, and resistors are recognised between 50 and 5,000 ohms. The timing window is 1, 10 or 20 seconds, with resolution of ±50 microseconds at 1 second, ±500 microseconds at 10 seconds and ±1.00 millisecond at 20 seconds. Timing accuracy is 0.05% of reading plus ±0.1 ms at the 1 second window.

The instrument triggers the breaker itself, with an initiate capacity of 30 A and 250 V AC or DC. A non-contact Hall-effect sensor reads the coil current from 0 to 20 A over a range from DC to 5 kHz, and a second non-contact sensor covers 0 to 100 A. The V1 input is analogue, 0 to 255 V with ±1 V sensitivity, and V2 detects voltage presence from 30 to 300 V. A digital travel transducer channel accepts a linear transducer from 0.0 to 60.0 inch, accurate to ±0.005 inch, or a rotary one from 0 to 360 degrees, accurate to ±0.006 degrees.

The instrument stores up to 200 test records and 100 test plans, and it can also write data to a USB flash drive. It connects to a PC over USB, with optional Bluetooth (9005-BT), and it comes with the VCBA S2 analysis software for Windows. The 9005-OT option adds on-line timing measurements.

The unit runs from 100 to 240 V AC at 50 or 60 Hz, drawing up to 3 A. It measures 47.0 x 35.7 x 17.6 cm and weighs 9.1 kg. It works from -10 to 50 °C and stores between -30 and 70 °C. The unit is built to UL/IEC 61010 and to the Canadian standard C22.2 No. 1010.1-92. A transport case is available for the instrument and the travel transducers.

Technical specifications

Typeportable circuit breaker analyser
Dry-contact channels3, main contact and insertion resistor contact in each
Timing windows1, 10 or 20 seconds
Timing resolution±50 microseconds at 1 s, ±500 microseconds at 10 s, ±1.00 ms at 20 s
Timing accuracy0.05% of reading ±0.1 ms at 1 s
Contact detectionclosed below 20 ohms, open above 5,000 ohms
Resistor detection50–5,000 ohms
Trigger input voltage30–300 V DC or peak AC
Voltage inputsV1 0–255 V, ±1 V sensitivity; V2 30–300 V
Breaker initiate capacity30 A, 250 V AC/DC
Coil current sensorHall-effect, non-contact, 0–20 A, DC to 5 kHz
Travel transducer channellinear 0.0–60.0 inch (±0.005 inch) or rotary 0–360 degrees (±0.006 degrees)
Memory200 test records, 100 test plans
InterfacesUSB, USB flash drive, optional Bluetooth
Displaybacklit LCD, 240 x 128 pixels
Power supply100–240 V AC, 50/60 Hz, 3 A
Dimensions and weight47.0 x 35.7 x 17.6 cm, 9.1 kg
Operating temperature-10 to 50 °C

Part numbers

Show all part numbers (2)

9005-UC, 9005-OT and 9005-BT

Request a price and lead time

DigiTMR S2 circuit breaker analyser with thermal printer. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does the analyser need a PC?

No. The DigiTMR S2 works stand-alone, showing results on its 240 x 128 pixel screen and printing them on the built-in printer. For analysis on a PC, the VCBA S2 software connects over USB.

Which contact movements can be measured?

With a digital travel transducer it measures stroke, velocity, over-travel and contact wipe, as well as contact time. A linear transducer covers 0.0 to 60.0 inch, and a rotary one covers 0 to 360 degrees.

Can the analyser detect resistor contacts?

Yes. Each of the three channels detects both the main contact and the insertion resistor contact, and resistors are recognised between 50 and 5,000 ohms.