CTVT Column-Type Variable Transformer, 40-1200 kVA, Regulation 0-100%
A column-type variable transformer for smooth adjustment of AC voltage under load in regulators, power supplies and stabilisers. It offers quasi-stepless regulation from 0 to 100%, a turn-to-turn voltage difference of no more than 0.7 V, and single-phase or three-phase versions.
- Type
- column-type variable autotransformer
- Power rating
- 40-1200 kVA
- Number of phases
- single or three
- Regulation
- quasi-stepless, 0-100%
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
This variable transformer is built for applications that need continuous adjustment of AC voltage under load, including voltage regulators, power supplies and test installations. The double current collector variant, called plus/minus, is intended for stabilisers in which a buck-boost transformer must regulate while shifting voltage polarity.
The coil assembly consists of an outer copper winding and internal compensation coils, all wrapped around a laminated steel core. Vacuum pressure impregnation (VPI) encapsulates the coils, which strengthens the column and spreads heat evenly. The winding face is exposed so that the turns can be seen, and it is nickel plated to give a wear resistant and corrosion free current path. Aluminium and steel frames carry the columns, giving a heavy duty and dependable unit.
Current is taken by carbon rollers 35 mm in diameter. Each roller moves onto the next turn before leaving the previous one, which keeps output voltage uninterrupted, and the turn-to-turn voltage difference is held to no more than 0.7 V. The rollers avoid the mechanical problems of sliding contacts and withstand more cycles because friction is lower. Each roller carries 25 A, and holders take three or four rollers, so a column face can deliver up to 100 A. In the plus/minus design, rollers sit on both sides of the column at opposite ends, giving two output circuits per column and doubling the kVA rating. A compensation winding beneath each commutating winding spreads the current evenly along the column, reducing voltage drop.
Rollers are moved by a motorised drive with a ball-screw, bevel gears and bearings in the housings, and chain drives are not used. The motor can be AC or DC and gives a fixed or variable rate. Typical regulation runs from 0 to 100% in one minute on the AC drive and 30 seconds on the DC drive, and other speeds are supplied to order. Micro switches limit the upper and lower travel. The range covers 40 to 1200 kVA in a modular design, with output adjustable from 0 to 100% of the input voltage, or up to 115% in step-up versions. Windings are delta and wye auto-wound as standard, the working frequency is 50-60 Hz, and continuous duty is available up to an ambient temperature of 40 degrees C.
Technical specifications
| Type | column-type variable autotransformer |
|---|---|
| Power rating | 40-1200 kVA |
| Number of phases | single or three |
| Regulation | quasi-stepless, 0-100% |
| Output voltage | 0-115% of input (with step-up) |
| Turn-to-turn voltage difference | no more than 0.7 V |
| Operating frequency | 50-60 Hz |
| Winding connection | delta and wye, auto-winding as standard |
| Current collectors | carbon rollers 35 mm, 25 A per roller |
| Drive | motorised, ball-screw with bevel gears |
| Regulation speed | 0-100% in 1 minute (AC), 30 seconds (DC) |
| Insulation | vacuum pressure impregnation (VPI) |
| Commutator path | nickel plated |
| Ambient temperature | continuous duty up to 40 degrees C |
Request a price and lead time
CTVT Column-Type Variable Transformer, 40-1200 kVA, Regulation 0-100%. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What regulation speed is achieved?
Typically 0-100% in one minute with the AC drive and in 30 seconds with the DC drive, and other speeds are supplied to order.
Can the output be higher than the input?
Yes, step-up versions give an output of 0-115% of the rated input voltage.
How much current can one column carry?
Each carbon roller carries 25 A, so a column face with four rollers provides up to 100 A, and the plus/minus design doubles the column's rating.