International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

CT-8000 S3 EHV breaker analyser with built-in 200 A source for dynamic resistance

The CT-8000 S3 is a fourth generation EHV breaker analyser with a built-in 200 A current source. In addition to contact timing and travel parameters, it measures static and dynamic contact resistance and carries out tests with earthing on both sides.

Type
portable circuit breaker analyser
Dry contact inputs
3 channels (9103-UC) or 6 channels (9104-UC)
Resistance measurement current
up to 200 A
Static and dynamic resistance range
0.1–1999 µΩ

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The CT-8000 S3 is used for complete checks of extra high and high voltage circuit breakers. Its main distinction from analysers without a current source is the measurement of dynamic contact resistance. The instrument passes a current of up to 200 A through the contacts while they are moving and records the change in resistance across the range 0.1–1999 µΩ, with an accuracy of ± 2 % of reading ± 5 µΩ. The same current is used to measure static resistance.

As in the other models of the series, the instrument measures the timing of main and resistor contacts, travel, speed, transition, bounce and dip across opening, closing, open-close, close-open and open-close-open operations. The 9103-UC version has 3 contact channels and the 9104-UC has 6. The measurement window is 1, 10 or 20 s, with resolution of ±50 µs in the 1 s window and timing accuracy of 0.05 % of reading ± 0.05 ms. Pre-insertion resistors are detected in the range 50–5000 Ω.

Testing with earthing on both sides improves personnel safety and shortens preparation time, and it uses three non-contact clip-on sensors. Measurements under voltage use three non-contact AC sensors rated 0–100 A and one DC sensor rated 0–20 A. The drive command goes out through a 30 A, 250 V AC/DC circuit, and the coil current is measured by a Hall effect sensor at 0–20 A.

For travel analysis there are three digital transducer channels with a linear range of 0–60 inches and a rotary range of 0–360 degrees, plus three resistive transducer inputs from 200 Ω to 10 kΩ. Memory holds 200 records and 100 programmes, with a USB memory stick port, a USB port for a PC and optional Bluetooth. The 128 x 240 pixel display and 4.5 inch thermal printer produce travel curves and tables.

The unit conforms to UL 6101A-1 and to the CAN/CSA C22.2 standard No 1010.1-92. Power input is 100–240 V AC, 10 A, 50/60 Hz. Dimensions are 40.6 x 29.9 x 35.6 cm and the mass is 9.98 kg. The operating range is -10 to +50 °C, storage is -30 to +70 °C, and humidity can reach 90 % at 40 °C.

Technical specifications

Typeportable circuit breaker analyser
Dry contact inputs3 channels (9103-UC) or 6 channels (9104-UC)
Resistance measurement currentup to 200 A
Static and dynamic resistance range0.1–1999 µΩ
Resistance accuracy± 2 % of reading ± 5 µΩ
Measurement windows1 s, 10 s, 20 s
Resolution± 50 µs (1 s), ± 500 µs (10 s), ± 1.0 ms (20 s)
Timing accuracy0.05 % of reading ± 0.05 ms in the 1 s window
Pre-insertion resistors50–5000 Ω
Start voltage24–300 V DC or peak AC
Drive control circuit30 A, 250 V AC/DC max.
Digital travel transducers3; 0–60 inches; 0–360 degrees
Under-voltage mode sensors3 × AC 0-100 A; 1 × DC 0-20 A
Earthing on both sides3 non-contact clip-on sensors
Memory200 records, 100 programmes
Power supply100-240 V AC, 10 A, 50/60 Hz
Dimensions40.6 x 29.9 x 35.6 cm
Weight9.98 kg

Part numbers

Show all part numbers (7)

TP4-CS, 9103-OT, 9103-BT, 9103-DG, 9103-SC, 9104-UC, 9103-UC

Request a price and lead time

CT-8000 S3 EHV breaker analyser with built-in 200 A source for dynamic resistance. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How does the CT-8000 S3 differ from the CT-7000 S3?

The CT-8000 S3 has a built-in 200 A source and measures static and dynamic contact resistance in the range 0.1–1999 µΩ.

What is the resistance measurement accuracy?

± 2 % of reading ± 5 µΩ at currents up to 200 A.

Is measurement under voltage supported?

Yes, with option 9103-OT the instrument uses three non-contact AC sensors rated 0–100 A and one DC sensor rated 0–20 A.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides