CT-7000 S3 digital circuit breaker analyser with 3 or 6 channels and travel analysis

The CT-7000 S3 is a fourth generation EHV circuit breaker analyser. It measures the timing of main and resistor contacts, travel, speed, transition, bounce and contact dip across every breaker operation, including the open-close-open cycle.

Type
portable circuit breaker analyser
Dry contact inputs
3 channels (9021-UC) or 6 channels (9100-UC)
Measurement windows
1 s, 10 s, 20 s
Resolution
± 50 µs (1 s), ± 500 µs (10 s), ± 1.0 ms (20 s)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The CT-7000 S3 is used for a complete assessment of extra high, high and medium voltage circuit breakers during commissioning and scheduled inspections. Contact analysis and motion analysis are carried out across opening, closing, open-close, close-open and open-close-open operations. The instrument drives the breaker itself: its control circuit switches 30 A at 250 V AC/DC, and the coil current is read by a non-contact Hall effect sensor over 0–20 A, from DC up to 5 kHz.

The instrument is supplied with 3 contact channels (9021-UC) or 6 channels (9100-UC). Each channel records the timing of both the main contact and the pre-insertion resistor contact. A contact counts as closed below 20 Ω and open above 5000 Ω, and pre-insertion resistors are detected in the range of 50–5000 Ω. All inputs are earthed and protected against electrostatic discharge until the test starts.

The measurement window is selectable at 1, 10 or 20 s, with resolution of ±50 µs, ±500 µs and ±1.0 ms respectively, and timing accuracy of 0.05 % of reading ± 0.05 ms within the 1 s window. Motion analysis uses three digital transducer channels: a linear range of 0–60 inches with steps of ±0.01 inch, a rotary range of 0–360 degrees with steps of ±0.36 degree, and three resistive transducer inputs from 200 Ω to 10 kΩ. Input V1 records 0–250 V DC or peak AC, while V2 and V3 detect the presence of 24–255 V. The difference between contact points during slow closing is measured separately.

Memory holds 200 records and 100 test programmes. There is a USB memory stick port, a USB port for a PC and an optional Bluetooth wireless interface. The display is 128 x 240 pixels, and a 4.5 inch thermal printer prints travel curves and results tables. Options include a live voltage measurement mode, a test mode for breakers earthed on both sides, and transport cases.

Power input is 100–240 V AC, 3 A, 50/60 Hz. Dimensions are 53 x 20 x 35 cm and mass is 6.8 kg. The operating temperature runs from -10 to +50 °C, and storage from -30 to +70 °C. The design conforms to UL 6101A-1 and to the CAN/CSA C22.2 standard No 1010.1-92.

Technical specifications

Typeportable circuit breaker analyser
Dry contact inputs3 channels (9021-UC) or 6 channels (9100-UC)
Measurement windows1 s, 10 s, 20 s
Resolution± 50 µs (1 s), ± 500 µs (10 s), ± 1.0 ms (20 s)
Timing accuracy0.05 % of reading ± 0.05 ms in the 1 s window
Contact detectionclosed below 20 Ω, open above 5000 Ω
Pre-insertion resistors50–5000 Ω
Start voltage24–300 V DC or peak AC
OperationsO, C, O-C, C-O, O-C-O
Drive control circuit30 A, 250 V AC/DC max.
Coil current sensorHall effect, 0–20 A, DC ... 5 kHz AC
Digital travel transducers3; 0–60 inches; 0–360 degrees
Resistive transducers3, 200 Ω – 10 kΩ
Voltage inputsV1 0–250 V; V2, V3 24–255 V
Memory200 records, 100 programmes
DisplayLCD 128 x 240 pixels
Printerthermal, 4.5 inch
Power supply100-240 V AC, 3 A, 50/60 Hz
Dimensions and weight53 x 20 x 35 cm; 6.8 kg

Part numbers

Show all part numbers (6)

9021-BT, 9021-OT, 9021-DG, 9021-SC, 9100-UC, 9021-UC

Request a price and lead time

CT-7000 S3 digital circuit breaker analyser with 3 or 6 channels and travel analysis. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What separates the 9021-UC and 9100-UC?

The number of contact channels: the 9021-UC has 3 and the 9100-UC has 6, and each channel records both the main and the resistor contact.

Which motion parameters does the instrument measure?

Travel, speed, transition, bounce and contact dip, using either three digital travel transducers or three resistive transducers.

Can breakers earthed on both sides be tested?

Yes, option 9021-DG covers that, while option 9021-OT covers measurements under voltage.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides