CT-7000 S3 digital circuit breaker analyser with 3 or 6 channels and travel analysis
The CT-7000 S3 is a fourth generation EHV circuit breaker analyser. It measures the timing of main and resistor contacts, travel, speed, transition, bounce and contact dip across every breaker operation, including the open-close-open cycle.
- Type
- portable circuit breaker analyser
- Dry contact inputs
- 3 channels (9021-UC) or 6 channels (9100-UC)
- Measurement windows
- 1 s, 10 s, 20 s
- Resolution
- ± 50 µs (1 s), ± 500 µs (10 s), ± 1.0 ms (20 s)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The CT-7000 S3 is used for a complete assessment of extra high, high and medium voltage circuit breakers during commissioning and scheduled inspections. Contact analysis and motion analysis are carried out across opening, closing, open-close, close-open and open-close-open operations. The instrument drives the breaker itself: its control circuit switches 30 A at 250 V AC/DC, and the coil current is read by a non-contact Hall effect sensor over 0–20 A, from DC up to 5 kHz.
The instrument is supplied with 3 contact channels (9021-UC) or 6 channels (9100-UC). Each channel records the timing of both the main contact and the pre-insertion resistor contact. A contact counts as closed below 20 Ω and open above 5000 Ω, and pre-insertion resistors are detected in the range of 50–5000 Ω. All inputs are earthed and protected against electrostatic discharge until the test starts.
The measurement window is selectable at 1, 10 or 20 s, with resolution of ±50 µs, ±500 µs and ±1.0 ms respectively, and timing accuracy of 0.05 % of reading ± 0.05 ms within the 1 s window. Motion analysis uses three digital transducer channels: a linear range of 0–60 inches with steps of ±0.01 inch, a rotary range of 0–360 degrees with steps of ±0.36 degree, and three resistive transducer inputs from 200 Ω to 10 kΩ. Input V1 records 0–250 V DC or peak AC, while V2 and V3 detect the presence of 24–255 V. The difference between contact points during slow closing is measured separately.
Memory holds 200 records and 100 test programmes. There is a USB memory stick port, a USB port for a PC and an optional Bluetooth wireless interface. The display is 128 x 240 pixels, and a 4.5 inch thermal printer prints travel curves and results tables. Options include a live voltage measurement mode, a test mode for breakers earthed on both sides, and transport cases.
Power input is 100–240 V AC, 3 A, 50/60 Hz. Dimensions are 53 x 20 x 35 cm and mass is 6.8 kg. The operating temperature runs from -10 to +50 °C, and storage from -30 to +70 °C. The design conforms to UL 6101A-1 and to the CAN/CSA C22.2 standard No 1010.1-92.
Technical specifications
| Type | portable circuit breaker analyser |
|---|---|
| Dry contact inputs | 3 channels (9021-UC) or 6 channels (9100-UC) |
| Measurement windows | 1 s, 10 s, 20 s |
| Resolution | ± 50 µs (1 s), ± 500 µs (10 s), ± 1.0 ms (20 s) |
| Timing accuracy | 0.05 % of reading ± 0.05 ms in the 1 s window |
| Contact detection | closed below 20 Ω, open above 5000 Ω |
| Pre-insertion resistors | 50–5000 Ω |
| Start voltage | 24–300 V DC or peak AC |
| Operations | O, C, O-C, C-O, O-C-O |
| Drive control circuit | 30 A, 250 V AC/DC max. |
| Coil current sensor | Hall effect, 0–20 A, DC ... 5 kHz AC |
| Digital travel transducers | 3; 0–60 inches; 0–360 degrees |
| Resistive transducers | 3, 200 Ω – 10 kΩ |
| Voltage inputs | V1 0–250 V; V2, V3 24–255 V |
| Memory | 200 records, 100 programmes |
| Display | LCD 128 x 240 pixels |
| Printer | thermal, 4.5 inch |
| Power supply | 100-240 V AC, 3 A, 50/60 Hz |
| Dimensions and weight | 53 x 20 x 35 cm; 6.8 kg |
Part numbers
Show all part numbers (6)
9021-BT, 9021-OT, 9021-DG, 9021-SC, 9100-UC, 9021-UC
Request a price and lead time
CT-7000 S3 digital circuit breaker analyser with 3 or 6 channels and travel analysis. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What separates the 9021-UC and 9100-UC?
The number of contact channels: the 9021-UC has 3 and the 9100-UC has 6, and each channel records both the main and the resistor contact.
Which motion parameters does the instrument measure?
Travel, speed, transition, bounce and contact dip, using either three digital travel transducers or three resistive transducers.
Can breakers earthed on both sides be tested?
Yes, option 9021-DG covers that, while option 9021-OT covers measurements under voltage.