CBCT programmable DC source for breaker coil tests, up to 80 A
The CBCT supplies adjustable DC voltage from 5 % to 95 % of the substation battery voltage for testing breaker trip and close coils. It holds up to 80 A with voltage regulation of 2 % or better, and a built-in single-channel timer measures operating time.
- Type
- programmable DC power supply
- Input voltage
- 20–300 V DC, 20 A fuse
- Output voltage
- 5–95 % of input voltage, 2 % regulation at up to 80 A
- Outputs
- 1 continuous and 1 pulsed DC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The CBCT programmable source is intended for testing the trip and close coils of circuit breakers at substations. Its primary job is establishing the minimum coil operating voltage: the coil voltage is lowered to a set level and the operator checks whether the mechanism still trips.
The CBCT draws its energy from the station DC battery and electronically converts it into a programmable output between 5 % and 95 % of the input voltage. While the coil operates, the unit holds the current at up to 80 A with voltage regulation of 2 % or better. The input range of 20–300 V DC is protected by a 20 A fuse. Built-in input and output voltmeters cover 0–300 V DC with an accuracy of 1 % of reading ± 0.2 V.
The instrument provides two DC outputs, one continuous and one pulsed. The output shuts off if the current exceeds 80 A, or if 80 A flows for longer than 500 ms, which protects the coil from overheating. A built-in single-channel timer measures breaker operating time, and it can also serve other timing tasks. The timer range is 0.0000–999.999 s with an accuracy of 0.01 % ± 0.5 ms. It starts internally from coil voltage application, from a 20–240 V AC/DC voltage input or from a dry contact of 1–200 Ω, and it stops from a voltage input or a dry contact.
Readings appear on a backlit LCD with four lines of 20 characters, legible in both bright sunlight and dim light. Dimensions are 48 x 17 x 38 cm and mass is 11.3 kg. The operating range is -10 to 50 °C and storage is -30 to 70 °C. The design conforms to UL 6101A-1 and to the CAN/CSA C22.2 standard No 1010.1-92. The kit includes two sets of 1.83 m DC cables of #8 AWG cross-section, two 3.05 m timer leads, an earthing cable and a cable bag, and a transport case is available as an option.
Technical specifications
| Type | programmable DC power supply |
|---|---|
| Input voltage | 20–300 V DC, 20 A fuse |
| Output voltage | 5–95 % of input voltage, 2 % regulation at up to 80 A |
| Outputs | 1 continuous and 1 pulsed DC |
| Output protection | shut-off above 80 A or above 500 ms at 80 A |
| Voltmeters | input and output, 0–300 V DC, 1 % of reading ± 0.2 V |
| Timer range | 0.0000–999.999 s, accuracy 0.01 % ± 0.5 ms |
| Timer start | internal; 20–240 V AC/DC; dry contact 1–200 Ω |
| Timer stop | 20–240 V AC/DC; dry contact 1–200 Ω |
| Display | backlit LCD, 4 lines of 20 characters |
| Dimensions | 48 x 17 x 38 cm |
| Weight | 11.3 kg |
| Operating temperature | -10...50 °C |
| Storage temperature | -30...70 °C |
| Safety | UL 6101A-1 and CAN/CSA C22.2 standard No 1010.1-92 |
Part numbers
Show all part numbers (1)
9063-CT
Request a price and lead time
CBCT programmable DC source for breaker coil tests, up to 80 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Where does the CBCT take its coil supply from?
From the substation DC battery at 20–300 V DC, and the unit produces an output between 5 % and 95 % of the input voltage.
How is the coil protected during a test?
The output shuts off if the current exceeds 80 A, or if 80 A flows for longer than 500 ms.
Can breaker operating time be measured?
Yes, the built-in single-channel timer, with a range of 0.0000–999.999 s and an accuracy of 0.01 % ± 0.5 ms, starts from the coil, a voltage input or a dry contact.