CBA 3000 circuit breaker analyser with six 200 A micro-ohmmeters and BSG function

The CBA 3000 carries out all breaker tests in one housing, covering timing, travel and speed analysis, simultaneous static and dynamic contact resistance, and tests with earthing on both sides and at reduced voltage. No external modules are required.

Micro-ohmmeter current
200, 150, 100, 50, 25 A
Resistance ranges
250 µΩ, 1 mΩ, 10 mΩ, 50 mΩ, 500 mΩ
Minimum resolution
0.1 µΩ
Accuracy (250 µΩ and 1 mΩ)
0.2 % of reading ± 0.2 % of range

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The CBA 3000 is designed to test circuit breakers through a single connection. Once the cables are attached, the instrument runs every required test automatically. It measures opening and closing times, pole discrepancy, three-phase first opening, coil currents, motor current and power, static and dynamic contact resistance, travel and speed, and SF6 pressure. It also performs an automatic minimum trip coil voltage check.

BSG capability for breakers earthed on both sides is built in and needs no external units. The instrument makes up to six simultaneous static and dynamic resistance measurements, each with 200 A DC. Micro-ohmmeter current is selectable at 200, 150, 100, 50 or 25 A, with ranges from 250 µΩ to 500 mΩ, a minimum resolution of 0.1 µΩ, and an accuracy of 0.2 % of reading ± 0.2 % of range on the 250 µΩ and 1 mΩ ranges. The maximum test voltage is 5 V.

The instrument provides 16 contact inputs, expandable to 24 as an option. They can be configured as main, resistor or auxiliary inputs and are grouped into 8 or 12 isolated pairs. Pre-insertion resistance can be measured from 30 Ω to 10 kΩ. There are two, four or six coil control circuits, each rated up to 300 V DC and 60 A DC or 300 V AC and 42 A AC, with timing accuracy of 0.025 % ± 20 µs. Sampling reaches 100 kHz. For travel analysis there are three analogue linear or rotary transducer inputs and three RS422 digital inputs for transducers of up to 5000 pulses per revolution.

Eight analogue inputs measure battery voltage, motor current, pressure transducer signals and other quantities in ranges of 300 V AC (420 V DC peak), 10 V DC and 1 V DC, with 16-bit resolution. The colour display has 800 x 480 pixels, and the 256 MB memory holds about 1000 results and up to 256 test sequences. The TDMS software package handles analysis, archiving and report generation, and a library of standard test programmes is supplied with the instrument.

Power input is 85–265 V AC at 47–63 Hz or 120–350 V DC, with consumption up to 360 VA. The aluminium case measures 407 x 450 x 230 mm and weighs 15 kg. The operating range is -10 to 55 °C, storage is -20 to 70 °C, relative humidity is 5–95 % without condensation, and the protection rating is IP 2X.

Technical specifications

Micro-ohmmeter current200, 150, 100, 50, 25 A
Resistance ranges250 µΩ, 1 mΩ, 10 mΩ, 50 mΩ, 500 mΩ
Minimum resolution0.1 µΩ
Accuracy (250 µΩ and 1 mΩ)0.2 % of reading ± 0.2 % of range
Simultaneous resistance measurementsup to 6, 200 A DC each
Contact inputs16, option 24
Pre-insertion resistor values30 Ω ... 10 kΩ
Coil control circuits2, 4 or 6
Coil control300 V DC, 60 A DC; 300 V AC, 42 A AC
Coil current ranges3; 10; 60 A
Timing accuracy0.025 % ± 20 µs
Sampling rateup to 100 kHz
Analogue inputs8; 300 V AC (420 V DC peak), 10 V DC, 1 V DC; 16 bit
Digital transducers3, RS422, up to 5000 pulses per revolution
Displaycolour, 800 x 480 pixels
Memory256 MB, about 1000 results
Power supply85–265 V AC, 47-63 Hz; 120–350 V DC; up to 360 VA
Dimensions407 x 450 x 230 mm
Weight15 kg

Part numbers

Show all part numbers (4)

79178, 75178, 20178, 21178

Request a price and lead time

CBA 3000 circuit breaker analyser with six 200 A micro-ohmmeters and BSG function. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Are external modules needed for BSG testing?

No, the function for testing a breaker earthed on both sides is built into the CBA 3000.

How many contacts can be measured at the same time?

Up to 16 contact inputs, or 24 with the option, and resistance is measured on up to 6 channels at once, each with 200 A DC.

Which coils can be controlled?

Up to 6 coil control circuits at up to 300 V DC and 60 A, or 300 V AC and 42 A.