CBA 1000 circuit breaker analyser with 200 A built-in micro-ohmmeter
The CBA 1000 measures timing, travel and contact speed of medium and high voltage circuit breakers, together with static and dynamic contact resistance at currents up to 200 A. It runs standalone and needs no connected computer for testing.
- Main contact inputs
- 6 (2 breaks per phase)
- Resistor contact inputs
- 6
- Auxiliary inputs
- 4
- Coil control circuits
- 2 (1 opening, 1 closing), option 4
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The CBA 1000 is used during maintenance and commissioning of medium, high and extra high voltage circuit breakers at substations. It records closing and opening operating times, pole discrepancy, coil and motor currents, and the static and dynamic resistance of the main contacts. It also tests the minimum voltage at which the trip coil operates, and measures contact travel and speed.
Connection points comprise six inputs for main contacts with two breaks per phase, six inputs for contacts fitted with resistors and four auxiliary timing inputs. The analogue inputs have 16-bit resolution and accept displacement transducers as well as voltage signals. Two coil control circuits are standard, one for opening and one for closing, with an option to extend to four. Coil current ranges are 2.5, 10 and 25 A, with control voltage up to 300 V DC. The sampling rate can be set between 20 Hz and 20 kHz, and recording lasts up to 200 s. Cross triggering lets up to four CBA 1000 units be synchronised for breakers with several breaks.
The built-in micro-ohmmeter measures resistance with a test current of 200 A, 100 A or 20 A across the 200 µΩ, 1 mΩ, 10 mΩ and 100 mΩ ranges, with 1 µΩ resolution. Results appear on a 320 x 240 pixel display with a 122 x 92 mm active area, and the unit stores 250 results and 64 preset test programmes. USB and RS232 ports handle communication with a PC for archiving.
Optional extras include an internal 58 mm thermal printer, an external printer for 112 mm paper, an option for minimum trip coil testing on battery systems rated up to 250 V or 70 V, linear transducers TLH150, TLH225, TLH500, LWG150, LWG 225 and LWG 500, a rotary transducer and a Hall effect clip-on transformer. Power comes from 85–265 V AC at 50–60 Hz, from 100–350 V DC, or from a built-in Ni-Mh battery that gives 4 hours of breaker testing or 1 hour of micro-ohmmeter use, with 8 hours needed to recharge. The aluminium case measures 400 x 300 x 240 mm and weighs 10 kg, or 11 kg with the micro-ohmmeter. Rated IP 2X to EN60529, it operates from 0 to +55 °C and stores from -40 to +70 °C.
Technical specifications
| Main contact inputs | 6 (2 breaks per phase) |
|---|---|
| Resistor contact inputs | 6 |
| Auxiliary inputs | 4 |
| Coil control circuits | 2 (1 opening, 1 closing), option 4 |
| Coil control voltage | up to 300 V DC |
| Coil current ranges | 2.5; 10; 25 A |
| Analogue input resolution | 16 bit |
| Sampling rate | 20 Hz ... 20 kHz |
| Recording duration | up to 200 s |
| Micro-ohmmeter current | 200 A, 100 A, 20 A |
| Resistance ranges | 200 µΩ; 1 mΩ; 10 mΩ; 100 mΩ |
| Micro-ohmmeter resolution | 1 µΩ |
| Memory | up to 250 results, 64 programmes |
| Interfaces | USB, RS232 |
| Power supply | 85–265 V AC, 50-60 Hz; 100–350 V DC; Ni-Mh battery |
| Operating temperature | 0...+55 °C |
| Dimensions | 400 x 300 x 240 mm |
| Weight | 10 kg; 11 kg with micro-ohmmeter |
| Protection rating | IP 2X |
Part numbers
Show all part numbers (13)
PII10166, PII20166, PII30166, PII40166, PII50166, PII60166, PII70166, PII80166, PII31166, PII51166, PII71166, PII81166, PII61166
Request a price and lead time
CBA 1000 circuit breaker analyser with 200 A built-in micro-ohmmeter. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the test need a computer?
No, the CBA 1000 works standalone, with tests set and results assessed on the instrument display. A PC can be connected through USB or RS232 for archiving.
How is a breaker with several breaks per phase tested?
Cross triggering synchronises up to four CBA 1000 units, and each unit has six main contact inputs and six resistor contact inputs.
Which current is used to measure contact resistance?
The built-in micro-ohmmeter injects 200 A, 100 A or 20 A and measures static and dynamic resistance with 1 µΩ resolution.