CBA 1000 circuit breaker analyser with 200 A built-in micro-ohmmeter

The CBA 1000 measures timing, travel and contact speed of medium and high voltage circuit breakers, together with static and dynamic contact resistance at currents up to 200 A. It runs standalone and needs no connected computer for testing.

Main contact inputs
6 (2 breaks per phase)
Resistor contact inputs
6
Auxiliary inputs
4
Coil control circuits
2 (1 opening, 1 closing), option 4

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The CBA 1000 is used during maintenance and commissioning of medium, high and extra high voltage circuit breakers at substations. It records closing and opening operating times, pole discrepancy, coil and motor currents, and the static and dynamic resistance of the main contacts. It also tests the minimum voltage at which the trip coil operates, and measures contact travel and speed.

Connection points comprise six inputs for main contacts with two breaks per phase, six inputs for contacts fitted with resistors and four auxiliary timing inputs. The analogue inputs have 16-bit resolution and accept displacement transducers as well as voltage signals. Two coil control circuits are standard, one for opening and one for closing, with an option to extend to four. Coil current ranges are 2.5, 10 and 25 A, with control voltage up to 300 V DC. The sampling rate can be set between 20 Hz and 20 kHz, and recording lasts up to 200 s. Cross triggering lets up to four CBA 1000 units be synchronised for breakers with several breaks.

The built-in micro-ohmmeter measures resistance with a test current of 200 A, 100 A or 20 A across the 200 µΩ, 1 mΩ, 10 mΩ and 100 mΩ ranges, with 1 µΩ resolution. Results appear on a 320 x 240 pixel display with a 122 x 92 mm active area, and the unit stores 250 results and 64 preset test programmes. USB and RS232 ports handle communication with a PC for archiving.

Optional extras include an internal 58 mm thermal printer, an external printer for 112 mm paper, an option for minimum trip coil testing on battery systems rated up to 250 V or 70 V, linear transducers TLH150, TLH225, TLH500, LWG150, LWG 225 and LWG 500, a rotary transducer and a Hall effect clip-on transformer. Power comes from 85–265 V AC at 50–60 Hz, from 100–350 V DC, or from a built-in Ni-Mh battery that gives 4 hours of breaker testing or 1 hour of micro-ohmmeter use, with 8 hours needed to recharge. The aluminium case measures 400 x 300 x 240 mm and weighs 10 kg, or 11 kg with the micro-ohmmeter. Rated IP 2X to EN60529, it operates from 0 to +55 °C and stores from -40 to +70 °C.

Technical specifications

Main contact inputs6 (2 breaks per phase)
Resistor contact inputs6
Auxiliary inputs4
Coil control circuits2 (1 opening, 1 closing), option 4
Coil control voltageup to 300 V DC
Coil current ranges2.5; 10; 25 A
Analogue input resolution16 bit
Sampling rate20 Hz ... 20 kHz
Recording durationup to 200 s
Micro-ohmmeter current200 A, 100 A, 20 A
Resistance ranges200 µΩ; 1 mΩ; 10 mΩ; 100 mΩ
Micro-ohmmeter resolution1 µΩ
Memoryup to 250 results, 64 programmes
InterfacesUSB, RS232
Power supply85–265 V AC, 50-60 Hz; 100–350 V DC; Ni-Mh battery
Operating temperature0...+55 °C
Dimensions400 x 300 x 240 mm
Weight10 kg; 11 kg with micro-ohmmeter
Protection ratingIP 2X

Part numbers

Show all part numbers (13)

PII10166, PII20166, PII30166, PII40166, PII50166, PII60166, PII70166, PII80166, PII31166, PII51166, PII71166, PII81166, PII61166

Request a price and lead time

CBA 1000 circuit breaker analyser with 200 A built-in micro-ohmmeter. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does the test need a computer?

No, the CBA 1000 works standalone, with tests set and results assessed on the instrument display. A PC can be connected through USB or RS232 for archiving.

How is a breaker with several breaks per phase tested?

Cross triggering synchronises up to four CBA 1000 units, and each unit has six main contact inputs and six resistor contact inputs.

Which current is used to measure contact resistance?

The built-in micro-ohmmeter injects 200 A, 100 A or 20 A and measures static and dynamic resistance with 1 µΩ resolution.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides