International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

CAP CAL calibration module for tan δ and capacitance checks on TD 5000 and TDX 5000

The CAP CAL verifies that the TD 5000 and TDX 5000 measure tan δ and capacitance correctly. Its core is a very high precision high voltage capacitor, supplied with a certificate from the calibration laboratory.

Type
calibration module
Purpose
checking the accuracy of tan δ and capacitance measurements
Compatible test sets
TD 5000, TDX 5000
Core element
very high precision high voltage capacitor

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Engineers use the CAP CAL to check tan δ and capacitance measurements made by the TD 5000 and TDX 5000 test sets. Those sets assess the insulation of power transformers, bushings, instrument transformers, cables and capacitors. Condition assessment and year-on-year comparison depend on the accuracy of these readings, so periodic verification matters.

The module is built around a high voltage capacitor of very high precision. Its capacitance and dissipation factor were established in a laboratory, and the values are printed on a certificate delivered with the module. During a check the CAP CAL is connected to the test set in the same way as a test object, measurements are taken, and the capacitance and tan δ readings are compared with the certified figures. Any discrepancy indicates whether the measuring circuit still meets its stated accuracy.

Verification is carried out on site, so the test set never has to be shipped to a laboratory. It is worth doing before critical measurements, after transport or repair of the instrument, after the measuring cables have been replaced, and as part of internal control of measuring equipment in a service organisation. The certificate is kept with the module, and each result is logged so that the drift of the instrument can be followed over time.

The module works with the TD 5000 and TDX 5000 together with their matching cable sets. It needs no separate power supply or setup, so a check takes little time and can form part of the routine preparation of the test set for field work. The order code is 40175.

Technical specifications

Typecalibration module
Purposechecking the accuracy of tan δ and capacitance measurements
Compatible test setsTD 5000, TDX 5000
Core elementvery high precision high voltage capacitor
Documentcertificate from the calibration laboratory
Place of checkon site, together with the test set

Part numbers

Show all part numbers (1)

40175

Request a price and lead time

CAP CAL calibration module for tan δ and capacitance checks on TD 5000 and TDX 5000. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which instruments is the CAP CAL designed for?

It is designed for checking the accuracy of tan δ and capacitance measurements made by the TD 5000 and TDX 5000 test sets.

What is the check result compared against?

Against the capacitance and tan δ values listed on the calibration laboratory certificate supplied with the module.

When is a check worth carrying out?

Before critical measurements, after transport or repair of the test set, and after the measuring cables have been replaced.