International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

CAL4U universal partial discharge calibrator, charge from 1 to 10000 pC

The CAL4U calibrates partial discharge measurements. A rotary switch selects the charge from the series 1, 2, 5, 10, 20, 50, 100, 200, 500, 1000, 2000, 5000 or 10000 pC.

Type
partial discharge calibrator
Charge range
1 to 10000 pC
Charge values
1, 2, 5, 10, 20, 50, 100, 200, 500, 1000, 2000, 5000, 10000 pC
Charge unit
pC

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The CAL4U is auxiliary equipment for partial discharge measurement in high voltage insulation. Engineers use it before partial discharge tests on cables, transformers, bushings, metal-enclosed switchgear, motors and generators. It is equally useful in laboratories and on production lines during insulation acceptance tests.

The method is straightforward. The calibrator injects a pulse of known charge into the measuring circuit, and the partial discharge instrument scales its readings against that pulse. Results are then expressed in picocoulombs and compared with the limits set for the specific test object. Calibration should be repeated whenever the connection arrangement, the test object or the coupling device changes, because each of these alters the transfer ratio of the circuit.

A single rotary switch selects the calibrated charge, with values from 1 to 10000 pC. The lower values suit sensitivity checks on objects with small capacitance, while the higher charges cover objects that produce strong discharges or have considerable capacitance. One instrument therefore takes the place of a set of separate calibrators, each fixed to one value.

The calibrator is connected in parallel with the test object with the high voltage removed. Once calibration is complete it is disconnected, and only then is the test voltage applied, which protects the calibrator and follows standard partial discharge practice. CAL4U is intended for use with dedicated partial discharge detectors and with other instruments that work on the apparent charge method.

Technical specifications

Typepartial discharge calibrator
Charge range1 to 10000 pC
Charge values1, 2, 5, 10, 20, 50, 100, 200, 500, 1000, 2000, 5000, 10000 pC
Charge unitpC
Value selectionrotary switch
Purposecalibration of partial discharge measurements

Request a price and lead time

CAL4U universal partial discharge calibrator, charge from 1 to 10000 pC. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which charge values can be set?

The rotary switch offers 1, 2, 5, 10, 20, 50, 100, 200, 500, 1000, 2000, 5000 or 10000 pC.

When should calibration be repeated?

Each time the connection arrangement, the test object or the coupling device changes, because these affect the transfer ratio of the measuring circuit.

Can the calibrator stay connected under voltage?

No. Calibration is carried out with the high voltage removed, after which the calibrator is disconnected and only then is the test voltage applied.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides