The BUX 2000, BUX 3000 and BUX 5000 act as current units of the eKAM primary injection system, supplying an output current of 2000, 3000 or 5000 A. Each module contains a power transformer and a measuring current transformer, which passes the output value to the eKAM control unit.
- Output current
- 2000, 3000 and 5000 A
- AC output voltage
- up to 220 V
- Output frequency
- 15 to 500 Hz
- BUX 3000 output power
- 1800 VA continuous; 5200 VA peak for 10 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The BUX current boosters work with the eKAM primary injection system when testing current and voltage transformers, circuit breakers and protective relays at substations. Typical checks include transformation ratio, burden and polarity of current transformers, along with breaker tests. Paired with the STLG kit, the same setup also measures earthing system resistance, touch and step voltages to EN50522 and EN61936-1, line impedance, and the zero sequence and mutual coupling coefficients of overhead lines.
Inside each booster, a power transformer produces the high current, low voltage output, while a measuring current transformer records that output and feeds the reading to the eKAM control unit. The control unit regulates the AC output up to 220 V, and the frequency can be varied from 15 to 500 Hz. Several BUX units may be linked to one eKAM, but only one at a time, so they are used in turn. They can be ordered with the system or added later.
The three versions differ in output current: 2000 A for the BUX 2000, 3000 A for the BUX 3000 and 5000 A for the BUX 5000. The BUX 2000 and BUX 3000 both measure 190 mm across and 120 mm high, while the BUX 5000 is 200 mm in diameter and 170 mm high. The BUX 3000 delivers 1800 VA continuously and 5200 VA peak for 10 s. Each set includes 95 mm² cables: four of 2 m for the BUX 2000, four of 1.2 m for the BUX 3000 and twelve of 0.8 m for the BUX 5000. A 20 m power cable, a 20 m measurement cable and 400 A current clamps are also supplied.
Mains supply is 100–230 V ±15 %, 50–60 Hz, with a maximum draw of 16 A. The unit operates between -10 and 55 °C, can be stored between -20 and 70 °C, and tolerates 5–95 % relative humidity without condensation. Protection is rated IP 2X. The equipment complies with EN61326-1:2013 and CEI EN61010-1:2010 and with Directives 2014/30/EU and 2014/35/EU.
Technical specifications
| Output current | 2000, 3000 and 5000 A |
|---|---|
| AC output voltage | up to 220 V |
| Output frequency | 15 to 500 Hz |
| BUX 3000 output power | 1800 VA continuous; 5200 VA peak for 10 s |
| BUX 2000/3000 dimensions | diameter 190 mm, height 120 mm |
| BUX 5000 dimensions | diameter 200 mm, height 170 mm |
| BUX 2000 cables | 4 pcs, 95 mm², 2 m |
| BUX 3000 cables | 4 pcs, 95 mm², 1.2 m |
| BUX 5000 cables | 12 pcs, 95 mm², 0.8 m |
| Power and measurement cable | 20 m |
| Current clamps | 400 A |
| Supply voltage | 100-230 V ± 15 %; 50-60 Hz |
| Maximum current draw | 16 A |
| Operating temperature | -10...55 °C |
| Storage temperature | -20...70 °C |
| Relative humidity | 5-95 %, non-condensing |
| Protection rating | IP 2X |
| Applicable standards | EN61326-1:2013 and CEI EN61010-1:2010 |
Part numbers
Show all part numbers (3)
56175, 50175, 63175
Request a price and lead time
BUX 2000, BUX 3000 and BUX 5000 current boosters up to 5000 A for eKAM. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can several boosters be connected to eKAM at the same time?
No, one or more BUX modules are connected to eKAM in turn, never simultaneously. They can be ordered together with the system or added at a later date.
How is the output current measured?
Each module has a built-in measuring current transformer, which sends the output current value to the eKAM control unit.
Which earthing tests can be carried out with the boosters?
With the STLG kit, earthing system resistance, touch and step voltages to EN50522 and EN61936-1, and line impedance can be measured.