BTS 200 MKII Battery Discharge Test System, up to 1300 A
A portable BTS 200 MKII system for testing battery banks by discharge. It measures battery voltage, discharge current and capacity. One module dissipates up to 16 kW, and with nine external loads the discharge current reaches 1300 A.
- Total current with external loads
- maximum 1300 A
- Battery nominal voltages
- 24 V, 48 V, 110 V and 240 V DC
- Battery voltage
- 18 to 270 V
- Discharge current per module
- 130 A (24 to 120 V DC); 70 A (220 to 240 V DC)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The BTS 200 MKII is used to test new and used batteries at power stations and substations. Batteries of various types supply standby power to relays, circuit breakers, measuring equipment and telephone exchanges, so they are tested regularly against international standards. The instrument discharges the battery in a set mode and determines its actual capacity.
A microprocessor controls all discharge parameters in real time. Constant current, constant power, current profile and manual adjustment modes are available, and a profile can be set in up to 20 steps. An interrupted test can be resumed from the point where it stopped. A graphic 128 x 64 dot display shows parameters, curves and results, data are stored in internal memory, and the built-in software can be updated from a PC.
One module gives a discharge current of up to 130 A at 24 to 120 V DC and up to 70 A at 220 to 240 V DC. Up to nine external ELU 200 MKII loads, or other BTS 200 units, can be connected to a BTS 200 MKII, giving a total current of up to 1300 A, and 10 modules in parallel dissipate up to 160 kW. External loads are controlled over a CAN bus, and a computer connects via USB 2.0. A current clamp or an external shunt records the real load of the object as an additional discharge, and the instrument monitors the total current.
The nominal battery ranges are 24, 48, 110 and 240 V DC, and the permitted battery voltage runs from 18 to 270 V. The unit can be powered from the battery itself, from 100 to 240 V AC at 50/60 Hz, or from an external 100 to 270 V DC source. Operating temperature is 0 to 40 °C, storage -25 to 70 °C, and relative humidity 5 to 95% without condensation. The housing measures 283 x 700 x 420 mm and weighs 39 kg, with handles and two wheels, and a 330 x 900 x 600 mm transport case is available. Compared with the earlier BTS 200, the weight has fallen from 48 kg to 39 kg and the number of discharge steps has risen from 10 to 20. The unit meets EN 61326-1 for electromagnetic compatibility and EN 61010-1 for electrical safety.
Technical specifications
| Total current with external loads | maximum 1300 A |
|---|---|
| Battery nominal voltages | 24 V, 48 V, 110 V and 240 V DC |
| Battery voltage | 18 to 270 V |
| Discharge current per module | 130 A (24 to 120 V DC); 70 A (220 to 240 V DC) |
| Power per module | 16 kW |
| Power of 10 modules | 160 kW |
| Discharge modes | constant current, constant power, current profile, manual adjustment |
| Display | graphic, 128 x 64 dots |
| Interfaces | USB 2.0; CAN for external loads |
| Power supply | 100 to 240 V AC, 50/60 Hz; 100 to 270 V DC; from battery |
| Operating temperature | 0 to 40 °C |
| Storage temperature | -25 to 70 °C |
| Relative humidity | 5 to 95%, non-condensing |
| Dimensions | 283 x 700 x 420 mm |
| Weight | 39 kg |
| Standards | EN 61326-1, EN 61010-1 |
Part numbers
Show all part numbers (7)
20167, 21167, 12167, 28167, PII18167, PII12167, PII21167
Request a price and lead time
BTS 200 MKII Battery Discharge Test System, up to 1300 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many modules can be combined for a high-power discharge?
Up to nine external ELU 200 MKII loads or other BTS 200 units can be connected, and 10 modules together dissipate up to 160 kW at up to 1300 A.
What powers the unit at the site?
The battery under test, a 100 to 240 V AC supply at 50/60 Hz, or an external 100 to 270 V DC source.
Can the real load be taken into account during discharge?
Yes, a current clamp or an external shunt measures the real load current, and the unit keeps the total discharge current at the selected mode.